Skip to main content
View as Markdown

Drivers

Available Drivers​

The following drivers are available for Ignition's OPC-UA module.

Allen-Bradley Ethernet​

The Allen-Bradley brand of programmable logic controllers (PLC) is a popular choice in many industries. Ignition can connect to the following Allen-Bradley controllers:

PLCCapability
Logix DriverConnect to Allen-Bradley Logix family devices, including devices with firmware v21+.
ControlLogixConnect to ControlLogix firmware v20 and prior processors.
CompactLogixConnect to CompactLogix firmware v20 and prior processors.
MicroLogixConnect to MicroLogix 1100, 1200, 1400 and 1500 series PLCs.
PLC5Connect to PLC5s via Ethernet.
SLCConnect to SLC 5/05s via Ethernet.

See the following links for detailed step-by-step instructions on how to connect to these PLCs:

Modbus​

The Modbus Driver module allows the Ignition OPC-UA server to communicate with any device that supports the Modbus protocol, that is, the Modbus TCP and Modbus RTU over TCP protocols.

The Modbus Driver module can connect directly to devices that support Ethernet communications or it can also connect to Modbus devices through a Gateway device.

See the following sections for detailed step-by-step instructions:

Siemens​

The Siemens Drivers module provides support for connecting to the following PLCs via TCP/IP using the S7 protocol:

  • S7-300
  • S7-400
  • S7-1200

For step-by-step instructions on how to connect to Siemens Drivers, see the Siemens page.

UDP and TCP​

The UDP driver is a strictly passive listener. The UDP driver is configured to listen to one or more ports on a given IP address.

The TCP driver is configured to connect to one or more ports on a given IP address. This driver can listen, as well as write back to the connected port.

Rules are configured that dictate how the incoming data is interpreted.

For step-by-step instructions on how to connect to TCP Drivers, see the UDP and TCP Driver page.

DNP3​

The DNP3 module allows the Ignition OPC-UA server to communicate with other devices that support the DNP3 protocol (DNP3 outstations).

See the following sections for detailed step-by-step instructions, see the DNP3 page.

Omron​

The Omron Driver module allows the Ignition OPC-UA server to communicate with NJ-series controllers.

More information on the Omron driver can be found on the Omron page.