Skip to main content
View as Markdown

system.gui.getDesktopHandles

This function is used in Python Scripting.

Description​

Gets a list of all secondary handles of the open desktops associated with the current client. In this case, secondary means any desktop frame opened by the original client frame.

Example: If the original client opened 2 new frames ('left client' and 'right client'), then this function would return ['left client', 'right client']

See the Multi-Monitor Clients page for more details.

Client Permission Restrictions​

This scripting function has no Client Permission restrictions.

Syntax​

system.gui.getDesktopHandles()

Parameters​

None

Returns​

PySequence - A list of window handles of all secondary Desktop frames.

Scope​

Client

Code Examples​

Example #1
# The following example list all handles (except the main client)
# in the client console (Help -> Diagnostics -> Console)
print system.gui.getDesktopHandles()
Example #2
# Create the header and fetch handle names
header = ["Desktop Names"]
handleList = system.gui.getDesktopHandles()

# change the handle name list into a column
handleColumn = [[name] for name in handleList]

# display the handle list in a table component
event.source.parent.getComponent('Handles Table').data = system.dataset.toDataSet(header, handleColumn)