Skip to main content
View as Markdown

toDate

This function is used by Ignition's Expression language..

Description​

Tries to coerce value into a Date. If value is a number or a string that represents a number, the number is treated as the number of milliseconds since the epoch, January 1, 1970, 00:00:00 GMT. If value is a string, it is parsed to see if it represents a date in one of the supported formats:

  • yyyy-MM-dd
  • MM/dd/yyyy
  • MM/dd/yyyy HH:mm:ss
  • hh:mm:ss a
  • hh:mm a
  • MM/dd/yyyy hh:mm:ss a
  • yyyy-MM-dd HH:mm:ss.SSS
  • yyyy-MM-dd HH:mm:ss
  • EEE MMM dd HH:mm:ss z yyyy
  • yyyyMMdd.HHmmssSSSZ

If not, type casting fails.The failover value must be a number or string with the same restrictions.

Syntax​

toDate(value[, failover])

  • Parameters

    • object value - The value to type cast into a date.

    • object failover - Optional. The failover value if type casting fails.

  • Results

    • date - The value type cast as a date.

Examples​

Code Snippet
toDate("2007-04-12 16:28:22") //returns April 12th, 2007, 4:28:22 PM