Write to the Present_Value attribute of an object with a custom priority level. 

To use this function, the BACnet driver must be installed.


 


This scripting function has no Client Permission restrictions.


system.bacnet.writeWithPriority(deviceName, objectType, objectId, value, priority)

  • Parameters

String deviceName The name of the configured BACnet/IP device instance to write from.

Integer objectType The numeric id of the objectType of the object instance being written to. See the objectType reference table below. 

Integer objectId The object instance number to write to.

Object value The value to write. Clearing a value can be accomplished by writing a None value. 

Integer priority The priority level to write the value at. Must be in the range [1...16].

  • Returns

nothing

  • Scope

Gateway



ObjectID
Analog Input0
Analog Output1
Analog Value2
Binary Input3
Binary Output4
Binary Value5
Device8
Large Analog Value46
Multi-State Input13
Multi-State Output14
Multi-State Value15





# Write a value of 'True' to Binary Value 1 with a Priority of 7

deviceName = 'BACnet Remote'
objectType = 5 # Binary Value
objectId = 1
value = True
priority = 7


system.bacnet.writeWithPriority(deviceName, objectType, objectId, value, priority)




# Values can be cleared by writing a None value. 

deviceName = 'BACnet Remote'
objectType = 5 
objectId = 1
value = None
priority = 7

system.bacnet.writeWithPriority(deviceName, objectType, objectId, value, priority)