Component Palette Icon:



On this page ...

This component is used to make runtime-configurable time-series charts. It is configured by defining a set of pens and axes. Pens can be many different styles, such as line, area, bar, and shape. This chart automatically creates controls for picking the time range and for hiding or displaying pens.

Features

  • Easy configuration
  • User-selectable set of pens
  • Automatic time-selection controls
  • SQL Query and/or SQLTags Historian data sources
  • Automatic SPC and calculated pen support
  • Zoom, Pan, X-Trace modes
  • Any number of Y-axes and subplots
  • Realtime or Historical

Pens  

There are three kinds of pens in the Easy Chart:

  1. Tag Historian Pens: These pens pull their data from the Historian system.
  2. Database Pens: These pens will automatically create SQL SELECT queries to pull data from a database table. Typically, this is a table that is the target of a Historical Transaction Group.
  3. Calculated Pens: These pens display a calculated dataset based off another pen, such as a moving average or Statistical Process Control (SPC) function such as the Upper  Control Limit (UCL).

Interface Elements

ElementDescription
PensAfter dragging a tag onto the Easy Chart, a Pen corresponding to the tag's value will appear in the Pens panel. Pens can be selected and deselected using the checkboxes. Clicking the X next to a pen will remove it from the Easy Chart.
Date Range

In Historical mode, the user is shown a Vision - Date Range component to pick the range of data to fetch and display. The initial values of this component are set through properties on the chart. In historical mode, the chart does not poll.

In Realtime mode, the user is instead given the ability to select an amount of time before the current timestamp: 

The chart will poll at a rate according to the Poll Rate parameter.

In Manual mode, no user input controls are displayed. The chart will use the values of its Start Date and End Date parameters to govern what data is displayed. The chart will poll at a rate according to the Poll Rate parameter.

Maximize 

Clicking this button will maximize the chart to fill the area of the component.

Print 

Clicking this button will print the chart.

Save to Excel 

Clicking this button will save the chart data as an Excel spreadsheet.

Properties

NameDescriptionProperty TypeScriptingCategory
3D X OffsetThe offset to use in the x direction for the '3D Line' pen style.int.xOffset3DPen Style Options
3D Y OffsetThe offset to use in the y direction for the '3D Line' pen style.int.yOffset3DPen Style Options
Allow Color ChangesIf true, pen colors can be set to different values.boolean.allowColorChangesBehavior
Allow Tag History InterpolationIf enabled and the query mode is not raw, the data will be interpolated for time spans with no data available.booleantagHistoryAllowInterpolationTag History
Auto ApplyIf true, user changes to pen visibility will occur immediately.boolean.autoApplyBehavior
Auto Axis PositioningIf true, axes alternate automatically between left and right, rather than being placed explicitly.boolean.autoPositionAxesBehavior
Auto Color ListThe list of colors to use if auto pen coloring is enabled.Color[].autoColorListBehavior
Auto Pen ColoringIf true, pens are assigned different colors automatically.boolean.autoColorPensBehavior
AxesThis Dataset defines all axes that can be used by the pens.Dataset.axesChart Configuration
Axis FontThe font for axis labels.Font.axisLabelFontAppearance
Background ColorThe background color of the component. See Color Selector.Color.backgroundAppearance
Bar MarginThe margin to use for the 'Bar' pen style.double.barMarginPen Style Options
BorderThe border surrounding this component. Options are: No border, Etched (Lowered), Etched (Raised), Bevel (Lowered), Bevel (Raised), Bevel (Double), Button Border, Field Border, Line Border, and Other Border. Note: The border is unaffected by rotation. Border.borderAppearance
Box FillFor historical-mode date range. The fill color for the selection box. Can be chosen from color wheel, chosen from color palette, or entered as RGB or HSL value. See Color Selector.Color.boxFillHistorical Range
Button SizeThe size of the utility button icons.int.utilityButtonSizeUtility Buttons
Bypass Tag History CacheIf true, tag history queries will not use the client history cache.boolean.tagHistoryBypassCacheTag History
Calculated PensThis Dataset defines the calculated pens for the chart.Dataset.calcPensChart Configuration
Chart BorderThe border for the chart itself.Border.chartBorderAppearance
Chart Mode

Affects the mode that the chart operates in; Manual Mode, Historical Mode, Realtime Mode.

Integer ValueCorresponding Mode
0Manual
1Historical
2Realtime
int.chartModeBehavior
Chart TitleSets an optional title to be displayed above the chart.String.titleAppearance
CursorThe mouse cursor to use when hovering over this component. Options are: Default, Crosshair, Text, Wait, Hand, Move, SW Resize, or SE Resize.int.cursorCodeCommon
DB PensThis Dataset defines all of the database pens for the chart.Dataset.pensChart Configuration
Date Editor BackgroundThe background color for the date editor. See Color Selector.Color.editorBackgroundColorAppearance
Date Editor ForegroundThe foreground color for the date editor. See Color Selector.Color.editorForegroundColorAppearance
Date RangeAffects the position of the date range control.int.dateRangeLocationLayout
Date Range BorderThe border for the date range control, if visible.Border.dateRangeBorderAppearance
Date StyleThe style to display dates in. For international support.int.dateStyleHistorical Range
Digital GapThe size of the gap to use between digital pens.double.digitalGapPen Style Options
Empty Group NameThe group name to use for pens that are not in a pen group.String.emptyGroupNameBehavior
End DateFor manual-mode. The end date to use for selecting pen dataDate.endDateData
FontFont of text on this component.Font.fontAppearance
Foreground ColorThe foreground color of the component. See Color Selector.Color.foregroundAppearance
Gap ThresholdThe relative threshold to use for determining continuity breaks for the 'Discontinous Line' pen style.double.gapThresholdPen Style Options
Gridline ColorThe color of the gridlines. See Color Selector.Color.gridlineColorAppearance
Gridline Dash PatternEnter a string of comma-delimited numbers which indicate the stroke pattern for a dashed line. For instance, "3,5" means three pixels on, five pixels off.String.gridlineDashPatternAppearance
Gridline WidthThe width (thickness) of the gridlines.float.gridlineWidthAppearance
Group PensIf true, pens will be grouped by their group name.boolean.penGroupingBehavior
High Density ColorFor historical-mode date range. The color used to indicate high data density. See Color Selector.Color.highDensityColorHistorical Range
Horiz GapThe horizontal spacing to use for the pen checkboxes.int.hGapLayout
Ignore Bad Quality DataIf true, causes the system to ignore any bad quality data.booleantagHistoryIgnoreBadDataTag History
Invert Time AxisIf true, the time axis values will increase from the right to left or from top to bottom depending on the Plot Orientation.boolean.invertTimeAxisLayout
LegendWhere the legend should appear, if any.int.legendLayout
Max SelectionFor historical-mode date range. The maximum size of the selected date range.String.maxSelectionSizeHistorical Range
Maximize PlotIf true, displays maximized plot.boolean.currentlyMaximizedLayout
Mouseover TextThe text that is displayed in the tooltip which pops up on mouseover of this component.String.toolTipTextCommon
NameThe name of this component.String.nameCommon
Outer Range EndFor historical-mode date range. The end date for the outer range.Date.outerRangeEndHistorical Range
Outer Range StartFor historical-mode date range. The start date for the outer range.Date.outerRangeStartHistorical Range
Pen Control BorderThe border for the pen control panel, if visible.Border.penBorderAppearance
Pen Control ModeThe style in which the pen control panel alters the chart configuration. In heavyweight mode, unchecked pens are not queried, so checking and unchecking pens refreshes the chart. In lightweight mode, all pens are constantly queried, so checking and unchecking pens is quick.int.penControlModeBehavior
Pen Control?Controls whether or not end-users can turn on and off pens.boolean.allowPenManipulationBehavior
Plot BackgroundThe background color for all plots, unless they override it. See Color Selector.Color.plotBackgroundAppearance
Plot OrientationThe plot orientation for all plots.int.plotOrientationLayout
Plot OutlineThe color to use for the plot outline. See Color Selector.Color.plotOutlineColorAppearance
Poll RateThe rate (in milliseconds) at which this chart's queries poll. Historical charts don't use this property.int.pollRateBehavior
Properties LoadingThe number of properties currently being loaded. (Read only. Usable in bindings and scripting.)int.propertiesLoadingUncategorized
Realtime TextFor realtime-mode date range. The text to display on the realtime date control.String.rtLabelRealtime Range
Selected X ValueThe selected domain axis value for X-Trace and Mark modes. (Read only. Usable in bindings and scripting.)String.selectedXValueUncategorized
Selection HighlightFor historical-mode date range. The focus highlight color for the selection box. See Color Selector.Color.selectionHighlightHistorical Range
Show DensityFor historical-mode date range. If true, a data density histogram will be shown in the date range.boolean.showHistogramHistorical Range
Show LoadingIf true, an animated indicator will be shown when data is loading.boolean.showLoadingBehavior
Show Maximize Button?If true, a small maximize button will be displayed next to the chart.boolean.showMaximizeUtility Buttons
Show Popup?If true, a popup menu will be shown on right-click that allows the user to change mode, print, save, etc.boolean.showPopupBehavior
Show Print Button?If true, a small print button will be displayed next to the chart..boolean.showPrintUtility Buttons
Show Save Button?If true, a small save button will be displayed next to the chart.boolean.showSaveUtility Buttons
Show Tooltips?If true, tooltips showing point values will be displayed on the chart.boolean.tooltipsBehavior
Show WarningsIf true, warnings generated during chart configuration will be printed to the console.boolean.showWarningsBehavior
Sort PensIf true, pens visibility checkboxes will be sorted.boolean.alphabetizePensLayout
Start DateFor manual-mode. The start date to use for selecting pen data.Date.startDateData
Startup RangeFor historical-mode date range. If startup mode is Automatic, this will be the starting range of time available for selection.String.startupRangeHistorical Range
Startup SelectionFor historical-mode date range. If startup mode is Automatic, this will be the starting selected range.String.startupSelectionHistorical Range
Subplot GapThe gap between subplots.double.subplotGapLayout
SubplotsThis Dataset defines all subplots' relative size and color.Dataset.subplotsChart Configuration
Tag History ResolutionThe number of datapoints to request for tag history pens. -1 means raw data, 0 means automatic, which uses the width of the chart.int.tagHistoryResolutionTag History
Tag History Resolution ModeThe mode used for the number of requested points. Fixed will use the Tag History Resolution Size, Natural will return a value per scanclass execution, Chart Width will be based on the actual width of the chart component, and Raw will be the raw data.inttagHistoryResolutionModeTag History
Tag PensThis Dataset defines all of the Tag History pens for the chart.Dataset.tagPensChart Configuration
Tick DensityFor historical-mode date range. This is multiplied by the width to determine the current ideal tick unit.float.tickDensityHistorical Range
Tick FontThe font for tick labels.Font.axisTickLabelFontAppearance
Time StyleThe style to display times of day. For international support.int.timeStyleHistorical Range
Title FontThe font for the optional chart title.Font.titleFontAppearance
Today ColorFor historical-mode date range. The color of the "Today Arrow" indicator. See Color Selector.Color.todayIndicatorColorHistorical Range
Total DatapointsThe number of datapoints being displayed by the graph. (Read only. Usable in bindings and scripting.)int.datapointsUncategorized
Track MarginFor historical-mode date range. The amount of room on either side of the slider track. May need adjusting of default font is changed.int.trackMarginHistorical Range
UnitFor realtime-mode date range. The selected unit of the realtime date control.int.unitRealtime Range
Unit CountFor realtime-mode date range. The number of units back to display.int.unitCountRealtime Range
Validate Scan Class ExecutionsCauses the tag history query to verify the scan class execution records, generating bad data for the time periods where the scanclasses did not execute.booleantagHistoryValidateScanclassTag History
Vert GapThe vertical spacing to use for the pen checkboxes.int.vGapLayout
VisibleIf disabled, the component will be hidden.boolean.visibleCommon
Where ClauseA snippet of where clause that will be applied to all pens, like "TankNum = 2".String.globalWhereClauseData
X Axis AutoRange?If true, the X axis will automatically fit the range of available data, if false, it will display a fixed range based on the start date and end date.boolean.xAxisAutoRangeBehavior
X Axis LabelThe label shown on the X Axis (time axis).String.xAxisLabelAppearance
X Axis MarginA margin for the upper and lower ends of the x axis, expressed as a percentage of the total range.double.xAxisMarginBehavior
X Axis VisibleShould the x-axis be displayed?boolean.xAxisVisibleAppearance
X-Trace Large Number FormatThe large decimal format for the x-trace value in the Easy Chart.String.xTraceLargeNumberFormatAppearance
X-Trace Number Format ThresholdIf the magnitude of the to-be-formatted value is below this threshold, then the X-Trace Small Number Format will be used.double.xTraceNumberFormatThresholdAppearance
X-Trace Small Number FormatThe small decimal format for the x-trace value in the Easy Chart.String.xTraceSmallNumberFormatAppearance

X-Trace Track Mouse

If set enabled, and the chart is set to X-Trace mode, the X-Trace will auto track the mouse position while the cursor is over the component. This is particularly useful when displaying the Easy Chart on a touchscreen.
booleanxTraceTrackMouseAppearance

Scripting

Component Functions

  • Description

This function save the chart's datasets as an Excel file. Returns a String of the complete file path chosen by the user, or None if the user canceled the save.

  • Parameters

String filename - The default file name for the Save dialog.

  • Return

String

  •  Description

This function will print the chart.

  • Parameters

Nothing

  • Return

Nothing

  •  Description

Sets the current mode for the chart.

  • Parameters

Int mode - The mode to set the chart to. The mode options are as follows:

0 : Zoom Mode. This is the default mode, where the user can draw a zoom rectangle with the mouse pointer.

1 : Pan Mode. This mode lets the user use the mouse pointer to pan the chart to the left and right.

3 : Mark mode. This mode lets the user click near a datapoint to annotate the point with its X and Y value.

4 : X-Trace mode. This mode lets the user click and drag on the chart to see all values that fall along that X value.

  • Return

Nothing

  •  Description

returns an Array List of datasets, representing the time series data of each type of pen.

  • Parameters

None

  • Return

Array List of datasets. Each dataset represents timeseries data for set of pens. The order of the datasets are listed below.

  • Index order of datasets

    IndexDataset
    0Tag Pens
    1Calculated Pens
    2Database Pens
    Python - Accessing the Tag Pens Dataset
    # This example will extract the Tag Pens series data that is already present in an Easy Chart, and pass it to a Power Table on the same window. 
    # This script could be placed on the Easy Chart's propertyChanged event.
    
    # Filter on the name of the property
    if event.propertyName == 'tagPens':
    	
    	# Wrap our dataset behavor in a function, so we can pass it to system.util.invokeLater
    	def func():
    		chart = event.source	
    
    
    		# Extract the datasets
    		datasets = chart.exportDatasets()	
    
    
    		# Pass the first dataset (index 0 contains data for Tag Pens) to the Power Table
    		event.source.parent.getComponent('Power Table').data = datasets[0]
    
    	# Using invokeLater to provide a delay. We want this to run after the chart has finished loading the new tag. 
    	system.util.invokeLater(func, 1000)

Extension Functions

  • Description

Provides an opportunity to perform further chart configuration via scripting. Doesn't return anything.

  • Parameters

Component self - A reference to the component that is invoking this function.

JFreeChart chart- A JFreeChart object. Refer to the JFreeChart documentation for API details.

  • Return

Nothing

  • Description

Provides an opportunity to configure the x-trace label. Return a string to override the default label.

  • Parameters

Component self - A reference to the component that is invoking this function.

JFreeChart chart - A JFreeChart object. Refer to the JFreeChart documentation for API details.

String penName - The name of the pen the x-trace label applies to.

int yValue - The y-value of the pen at the x-trace location.

  • Return

Nothing

  • Description

Called when the user has dropped rows from a power table on the chart. The source table must have dragging enabled.

  • Parameters

Component self - A reference to the component that is invoking this function.

Component sourceTable - A reference to the table that the rows were dragged from.

List rows - An array of the row indicies that were dragged, in the order they were selected.

Dataset rowData - A dataset containing the rows that were dragged.

  • Return

Nothing

  • Description

Called when the user has dropped tags from the tag tree onto the chart. Normally, the chart will add pens automatically when tags are dropped, but this default behavior will be suppressed if this extension function is implemented.

  • Parameters

Component self - A reference to the component that is invoking this function.

List paths - A list of the tag paths that were dropped on the chart.

  • Return

Nothing

Example - Pen Name Replacement
#This will take a tag that gets dropped from a Tag Browse Tree set in Realtime Tag Tree mode,
#and will replace the underscores in the name of the tag "_" and replace them with spaces.
tagPens = self.tagPens
	
for tag in paths:
	tagPath = tag.replace("default", "~")
	splitTag = tag.split("/")
	name = splitTag[-1].replace("_", " ")
		
	newRow = [name, tagPath, "MinMax", "Default Axis", 1, 1, system.gui.color(255, 85, 85, 255), "", 1, 1, 0, 1, 0, "", 0, 0, 0, 1, 0, 0]
		
	self.tagPens = system.dataset.addRow(tagPens, newRow)
Example - Group Name
#This will take a tag that gets dropped from a Tag Browse Tree set in Realtime Tag Tree mode,
#and will place it into a Pen Group titled "My Group Name".

tagPens = self.tagPens
groupName = "My Group Name"
for tag in paths:
		
	newRow = [name, tagPath, "MinMax", "Default Axis", 1, 1, system.gui.color(255, 85, 85, 255), "", 1, 1, 0, 1, 0, "groupName", 0, 0, 0, 1, 0, 0]
		
	self.tagPens = system.dataset.addRow(tagPens, newRow)

Customizers

Refer to the Vision - Easy Chart Customizer and the Using the Vision Easy Chart sections of the manual for examples and tutorials on how to use the Easy Chart Customizer. With the customizer, you can set up: