Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Current »

This function is used in Python Scripting.

Description

Writes a value to a tag. Note that this function writes asynchronously. This means that the function does not wait for the write to occur before returning - the write occurs sometime later on a different thread.

Client Permission Restrictions

This scripting function has no Client Permission restrictions.

Syntax

system.tag.write(tagPath, value, suppressErrors)

  • Parameters

String tagPath - The path of the tag to write to.

Object value - The value to write.

Boolean suppressErrors - A flag indicating whether or not to suppress errors. (optional, client-only).

  • Returns

int - 0 if the write failed immediately, 1 if it succeeded immediately, and 2 if it is pending.

  • Scope

All

Code Examples
Code Snippet
# This code would go on a property change event for a numeric text field to calculate and write a value to a tag.
 
if event.propertyName == intValue:
 calcValue = event.newValue * 2.5
 system.tag.write("Tanks/tankHiSP",calcValue)
  • No labels