Contents
Partner Programs
Sepasoft - MES Modules
Cirrus Link - MQTT Modules
Resources
Knowledge Base Articles
Inductive University
Forum
IA Support
SDK Documentation
Browses a folder path or UDT and returns Tag configuration information for each Tag within the specified path. This can be used to view event scripts, alarms, as well as any other configurable attribute on a Tag.
This function was removed from Ignition 8, and replaced by system.tag.getConfiguration.
This scripting function has no Client Permission restrictions.
system.tag.browseConfiguration(path, recursive)
String path - The path that will be browsed, typically to a folder or UDT instance. Leave blank to browse the root folder. A Tag Provider may be specified as follows: "[TagProvider]". If the Tag Provider is omitted, client scoped calls will be made against the project's default provider. Gateway scoped calls must include a Tag Provider. When browsing UDTs, specifying the UDT path will browse the Tags inside the UDT. To browse the UDT instance, specify the parent of the instance.
Boolean recursive - If true, will recursively search for Tags in folders. Each folder will return a 'tags' property containing the nested TagConfigurations in another list.
TagConfiguration[] - A list of TagConfiguration objects. Attributes on the object may be read by calling tag.get(propertyObject). A list of attributes with configuration information can be obtained by calling getProperties(). Only attributes with non-default values will appear in the attribute list.
All
If called in the gateway scope, a tag provider must be specified.
Method | Description |
---|---|
getAlarms() | Returns a list of AlarmDefinition objects. Calling getProperties() on the object will return a list of non-default alarm properties. |
getFolderPath() | Returns the path to the folder the Tag resides in. |
getFullPath() | Returns the Tag path. |
getName() | Returns the name of the Tag. |
getParameters() | Returns a BasicPropertySet of UDT parameters. Returns an empty list if called on a Folder. Parameters and their values may be accessed with '.property' and '.value' |
getProperties() | Returns a Java Hashmap of properties that have non-default values. Individual values may be specified by calling tag.get(propertyObject). |
getSubTags() | If called on a folder and the recursive parameter is True, returns a list of TagConfiguration objects pertaining to the nested nodes. Returns an empty list if called on a UDT instance or recursive is False. |
getTagType() | Returns the type of the node. Possible values are:
|
""" This example will browse the root of the Tag Provider named "default". For each tag found, prints the non-default properties. """ # Specify the folder to browse. Modify this line to filter on a specific folder. folderPath = "[default]" # Start a non-recursive browse, and stores the configuration data in a variable tagConfig = system.tag.browseConfiguration(folderPath, False) # Iterate through the configuration data for tag in tagConfig: # For each tag, retrieve a list of non-default properties. We check each iteration of tagConfig # because each tag can potentially have a different configuration propList = tag.getProperties() # Iterate through the list of properties for prop in propList: # Print the property name and value. print "Property '%s' has a value of '%s'" % (prop, tag.get(prop))
# Start a non-recursive browse, and stores the configuration data in a variable tagConfig = system.tag.browseConfiguration('[default]', False) # Iterate through the configuration data for tag in tagConfig: # Get the type of tag. tagType = tag.getTagType() # The DB tag type has multiple subtypes. To determine its real type, we need to examine it further if str(tagType) == 'DB': # Look at the properties of the DB tag, and iterate over them propList = tag.getProperties() for prop in propList: # Once we find the expressionType, we can examine this property to determine the actual tag type if str(prop) == 'expressionType': tagType = tag.get(prop) # If we found the type, then we don't need to check the rest of the properties break # If we didn't break out, then we didn't find expressionType. Thus, it's a memory tag else: tagType = 'Memory' print '%s has a tag type of %s' % (tag.getName(), tagType)