Search

User Manual

GETTING STARTED


MODULES AND PLATFORM


APPENDIX


TUTORIALS & HELPFUL TRICKS


GLOSSARY


STRATEGIC PARTNER LINKS

Sepasoft - MES Modules
Cirrus Link - MQTT Modules

RESOURCES

Inductive University
Ignition Demo Project
Knowledge Base Articles
Forum
IA Support
SDK Documentation
SDK Examples

ALL MANUAL VERSIONS

Ignition 8
Ignition 7.9
Ignition 7.8

Deprecated Pages

Skip to end of metadata
Go to start of metadata


The Vision Module comes with a host of built-in components that you can select from for use in your project. One thing that you'll find when working with components is there are a few different ways to manipulate and layout components on a window when working in the Designer. Here is a small sampling of the component available in Vision. See the Vision Components Appendix page for a complete list of components. 


This section introduces you to how to work with components so you can learn how to quickly select, move, resize, duplicate, and group components during the design process. 

On this page ...

IULocgo


Component Overview



Selecting Components

There are a number of different ways to select components within a window, each of which have their own advantages.

Mouse Selection

Using the mouse is the most common way to select components. Click the Selection  icon, then click on a component to select it. If the component you want to select is obscured by other components, hold down Alt and keep clicking, the selection will step down through the z-order. 

You can also select components using window-selection. Click-and-drag within a container to draw a selection rectangle. If you drag the window left-to-right, it will select all components that are completely contained within the rectangle. If you drag the window right-to-left, it will select all components that the rectangle touches. 

Lastly, you can start dragging a window selection and then hold down the Alt key to use touch selection. This will draw a line as you drag, and any components that the line touches will become selected. As you're using these techniques, components are given a yellow highlight border.


Tree Selection

By selecting nodes in the Project Browser you can manipulate the current selection. This is a handy way to select the current window itself, which is hard to click on since it is behind the Root container. However, you can click to it, using Alt-click to step down through the z-order. It is also the only way to select components that are invisible.



IULocgo


Selecting Components


Component Properties

Each component has a unique set of properties that can be set and modified within the Property Editor. A property is simply a named variable with a distinct type that affects something about the component's behavior or appearance. You can also create your own custom properties on the component, which act like variables that can store any information that you want on the component.

Data Types

There are a wide variety of datatypes across all of the Vision Module's components. Each property has a distinct type, which dictate what values will be allowed. Below are the common data types.


IULocgo


Component Properties


Numeric Types

Boolean

A true/false value. Modeled as 0/1 in Python. Technically, 0 is false and anything else is true.

ShortA 16-bit signed integer. Can hold values between -32,768 to 32,767, inclusive.
Integer/intA 32-bit signed integer. Can hold values between -2,147,483,648 to 2,147,483,647 inclusive.
LongA 64-bit signed integer. Can hold values between -9,223,372,036,854,775,808 to 9,223,372,036,854,775,807 inclusive.
FloatA 32-bit signed floating point number in IEEE 754 format.
DoubleA 64-bit signed floating point number in IEEE 754 format.

Non-Numeric Types

StringA string of characters. Uses UTF-16 format internally to represent the characters.
ColorA color, in the RGBA color space. Colors can easily be made dynamic or animated using Property Bindings or Styles.
DateRepresents a point it time with millisecond precision. Internally stored as the number of milliseconds that have passed since the "epoch", Jan 1st 1970, 00:00:00 UTC.
DatasetA complex data structure that closely mimics the structure of a database table. A Dataset is a two-dimensional matrix (also known as a table) of data organized in columns and rows. Each column has a name and a datatype.
FontA typeface. Each typeface has a name, size, and style.
BorderA component border is a visual decoration around the component's edges. You can make a border dynamic by using the Style Customizer, the toBorder() expression function, or scripting with the Java border object.


Manipulating Components

Manipulating components can be done with both the mouse and the keyboard. You can move components around, resize them, and rotate them.

Resizing

When you select the component you want to resize, they'll get eight resize-handles displayed around the edge of the selection. These handles look like double-sided arrows around the perimeter. Use the mouse to drag them to change the size of the components in the selection. To maintain the selection's aspect ratio, hold down Ctrl as you resize. To resize around the center of the current selection, hold down Shift. These can be used at the same time.

IULocgo


Manipulating Components

You can also resize the current selection using the keyboard. To nudge the right or bottom edge of the selection in or out, use Shift combined with the arrow keys, which resizes by the nudge distance, which defaults to one pixel at a time. To nudge the top or left edge of the selection, use Ctrl-Shift combined with arrow keys. To resize faster, hold the Alt key as well, to move the component the alt nudge distance, which defaults to ten pixels at a time.|

Moving

To move the component, simply drag it anywhere within the container's bounds. You can also move whatever is currently selected by holding down Alt while dragging, regardless of whether or not the mouse is over the current selection. This is important because it is the primary way to move a Container component. (Normally, dragging in a container draws a selection rectangle inside that container).

While a component is selected, you may also use the keyboard's arrow keys to move a component around the nudge distance. Just like resizing with the arrow keys, to move the alt nudge distance, use the Alt key. 

Duplicating

Components can be easily duplicated by dragging them as if you were going to move them and holding down the Ctrl key. This will drop a copy of the component at the desired drop location. It is often useful to also hold down Shift key as you do this to ensure exact alignment. You may also use the Ctrl-D shortcut to quickly duplicate a component in place.

Rotating

Shapes can be rotated directly using the selection tool. Other components cannot be rotated in this manner. To rotate a shape, first select it using the selection tool so that you see the resize handles around it. Then simply click on it once again and you'll see the rotation handles appear. Clicking (but not double-clicking) on selected shapes toggles back and forth between the resize handles and the rotation handles.

Once you see the rotation handles, simply start dragging one to rotate the shape or shapes. Holding down the Ctrl key will snap your rotation movements to 15° increments. When the rotation handles are present, there is also a small red crosshair handle that starts in the middle of the selection. This is the rotation anchor: the point that the selection will rotate around. You can drag it anywhere you'd like to rotate around a point other than the center of the shape.

Size and Position

Components can also be positioned and resized with the Size and Position window. This window allows you to type in an exact pixel size of the component as well as x/y coordinates that the component will be at (with the upper left point of the component moving to that point). To access the size and position window, right click on the component and select Size and Position.

Component Grouping

Shapes and components can be grouped together so that they act like a single component in the Designer. Grouping components is very similar to putting them in a Container. In fact, it is the same thing as cutting and pasting them into a perfectly-sized container and then putting that container into group mode, with one exception. If the group contains only shapes and no other kinds of components, it will be a special shape-group that has the ability to be rotated and has some other shape-like properties.

When components or shapes are in a group, clicking on them in the Designer will select the group instead of the shape. If you double-click on a group, it will become "super-selected", which will allow you to interact with its contents until you select something outside of that group. 

Groups can contain other groups, creating a nested structure. Groups themselves are also components, meaning that you can add custom properties to groups, bind them, and so on.

Difference between a Container and a Group

It is helpful to use Groups and Containers to organize the components on your window. You can select multiple components and right-click to convert them into a group, then right-click again convert that group to a container.

Layout works differently for groups. The layout setting for components and shapes inside a group is ignored. All members of a group act as if they are in relative layout with no aspect ratio restrictions. This special group-layout mode is also active when resizing a group inside of the Designer, whereas traditional (container) layout doesn't take effect in the Designer.


IULocgo


Component Grouping

 

Component Layout

Layout is the concept that a component's size and position, relative to its parent container's size and position, can be dynamic. This allows the creation of windows that resize gracefully using either Anchored or Relative layouts and can optionally keep the original aspect ratio. 

This is a very important concept because of the web-launched deployment of Vision clients - they often end up being launched on many different monitors with many different resolutions.

This is also important for components that have user-adjustable windows like popup windows. Imagine a popup window that is mostly displaying a large table or chart. If you're running on a large monitor, you may want to make the window bigger to see the table or chart easier. Of course, this is only useful if the table or chart actually gets larger with the window.

Changing a component's layout is as simple as right-clicking on the component and opening the Layout dialog box. You can also alter the default layout mode that gets assigned to new components. See Designer/Window Editing Properties.

There are two layout modes, and they are set on a per-component basis. Both affect the component's size and position relative to its parent container. The root container's size is dictated by the window size. To edit the layout of a component, right-click on the component and select Layout from the menu. the Layout Constraints window displays showing all the default settings. These default settings can be altered in the Project Properties.

Layout Modes

  • Relative
    This mode makes a component's size and location relative to its parent's size and location. When the parent changes size, the component changes accordingly. This creates components that auto-scale.
     
  • Anchored
    This mode makes the edge of a component's two axes (horizontal and vertical) anchored to the edge or edges of its parent.


IULocgo


Component Layout

 

 

Relative Layout

Relative Layout is the default mode. This is a simple and effective layout mode that simply keeps a component's size and position constant relative to its parent container, even when the parent container grows or shrinks. More precisely, it remembers the component's position and size as a percentage of its parent's bounds at the last time the window was saved. Relative Layout also has the option of scaling a component's font appropriately.

Example of Relative Layout

Note, that Relative Layout mode respects aspect ratio. So if the parent component is distorted, the contents will not be. The extra space is distributed evenly on both sides of the contents.

Relative layout preserves aspect ratio

Relative Layout Options

  • Maintain Aspect Ratio
    If selected, the component's original aspect ratio is preserved. Otherwise, it can stretch tall or wide.
     
  • Center
    When maintaining the aspect ratio, centers the component with respect to its parent.
     
  • Leading
    When maintaining the aspect ratio, aligns the component with the paper leading edge.
     
  • Trailing
    When maintaining the aspect ratio, aligns the component with the parent's trailing edge.
     
  • Scale Font
    If selected, the component's font will scale along with its size as the relative layout adjusts the component. This will override other font size settings. If this setting is applied to a Group, then all components in the group will use this setting.

Font Scaling

By default, font scaling is enabled on all components, but it can behave differently on some components so it’s good to test it out before putting it into production. You can change the default Component Layout settings in Project Properties under Vision > Design > Relative Layout Options.

Font Scaling on Individual Components

When individual components are dragged into a window, the following default Layout settings for each component are applied. All components on the window default to font scaling.

Font Scaling on Groups

When individual components are grouped together, the default Layout settings are applied to the new group component, and to each component in the group. All the components in the group default to font scaling.

 
 

Font scaling on individual components in a group can be disabled by selecting the group, and double clicking on a single component. You will get a red outline around the group, then you can select the individual component(s), and disable font scaling. Note: The individual component font scale setting takes precedence within a group.



When you remove the group (right-click and select Ungroup), all the individual components within that group will get reset to the default Layout settings including font scaling, even if font scaling was set differently.



Font Scaling on Containers

You can convert a group to a container to change the way scaling works. Ignition remembers the last Layout Settings you made to each individual component in that group prior to the conversion to a container (i.e., if any of the components had font scaling disabled, once the group is converted to a container, those same components will still have font scaling disabled).

 

Anchored Layout

Anchored Layout lets you specify various "anchors" for the component. The anchors dictate how far each of the 4 edges of the component stay from their corresponding edges in the parent container. 

Anchored Layout Options

  • North/South
    If one of these is selected, the distance between that edge of the component and that edge of the container is preserved. If both are selected, the component will stretch its height to maintain both distances.
     
  • West/East
    If one of these is selected, the distance between that edge of the component and that edge of the container is preserved. If both are selected, the component will stretch its width to maintain both distances.
     
  • Center Vertically
    When selected, both top and bottom buttons will be deselected. This option maintains the height of the component and centers it vertically in the container.
     
  • Center Horizontally
    When selected, both left and right buttons will be deselected. This option maintains the width of the component and centers it horizontally in the container.

     


For example, if you anchor top and left, then your component will stay a constant distance from top and left edges of its parent. Since you didn't specify an anchor for the right or bottom sides, they won't be affected by the layout.

Components anchored top and left

If you anchor bottom and right instead, the components will again stay the same size (since you didn't specify an anchor for their other edges, but they will stay a constant distance from their parent's right and bottom edges.

Components anchored bottom and right

Of course, you can mix and match the various modes for the different components in a given container. The following image shows the following:

  • The square uses a horizontal and vertical centering anchor. It is centered, and stays the same size.
  • The triangle is anchored south and west.
  • The circle is anchored north, west, south, and east. This means that its edges are all anchored and stay a fixed distance to each of its parent's edges, so it grows.

Components with various anchoring modes

 


In This Section ...

 

  • No labels