Scripting_function



Panel
titleDescription

Allows for invoking system.gui functions on a specific desktop.

See the Multi-Monitor Clients page for more details.


Panel
titleClient Permission Restrictions

This scripting function has no Client Permission restrictions.


Panel
titleSyntax

system.gui.desktop(handle)

  • Parameters

String handle The handle for the desktop to use. The screen index cast as a string may be used instead of the handle. If omitted, this will default to the Primary Desktop. Alternatively, the handle "primary" can be used to refer to the Primary Desktop.

  • Returns

WindowUtilities -  A copy of system.gui that will be relative to the desktop named by the given handle.

  • Scope

Client



Panel
titleCode Examples


Code Block
languagepy
titleCode Snippet
#The# The following example will make a message box appear on the Primary Desktop, 
#regardless# regardless of where the script originates from. 
system.gui.desktop().messageBox("This will appear on the Primary Desktop")


Code Block
languagepy
titleCode Snippet
#Retrieves# Retrieves a list of open windows in a specific Desktop. This example assumes a desktop with the handle "2nd Desktop" exists. 
name = "2nd Desktop"
#Returns# Returns a tuple of open windows in the Desktop named "2nd Desktop"
windows = system.gui.desktop(name).getOpenedWindows()

#Converts# Converts the tuple to a string, and shows the items in a message box
system.gui.messageBox(str(windows))