Quarantined data is data that has erred-out multiple times during attempts to forward it or data that could not be stored because of some configuration issues. It is removed from the forward queue to allow other data to pass. The most common reason for data quarantining is an invalid schema in the database for the data that is being stored. Quarantined data is held indefinitely until the issue is resolved, then you can either delete it or re-insert it into the queue. 

To

Handle

handle the

Quarantined Data

quarantined data

  1. From Status section of the Gateway, go to Connections > Store and Forward.

  2. Click the Details details tab next to a Store and Forward engine that you would like to see the quarantine data for. Here you will see any quarantined data , including the number of occurrences, a description of the where the items originated from, and the reason why the record was placed into the quarantine.  which are listed according to the order they got quarantined. Each set of data has the option to retry it, delete it, or export it for later use. If there are a lot of quarantined records, it may be a good idea to export and delete them so that the store and forward engine won't fill up and drop records.

  3. Fix the problem/error you found that caused the quarantine data.
  4. Click on retry, or if the data had been exported, import the data using the import tool and then retry. This way, you can ensure no data gets lost.

Image Added

Scroll HTML Exporter Ignore

Iulink

Description

URL https://www.inductiveuniversity.com/video/controlling-quarantine-data?r=/course/databases-in-ignition
NameControlling Quarantine Data

 

 Image Removed

Next_link

  • Store and Forward
  • Connections -