Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


The Tag Browser is the central location for interaction with all types of Tags on your system. It gives you full view of the Tags including the current value, datatype, and any traits.  When panels are in their default configuration in the Designer, the Tag Browser appears on the left side. 


As of release 8.1, the Tag Browser has been updated with a new design for ease of use. Tags and UDT Definitions now have their own tabs. The Tag Provider Selector enables you to view Tags for a specific Tag provider. There is a new interface for Creating Tags. Many other improvements have been integrated, including icons for each Tag type.



On_this_page



Scroll HTML Exporter Ignore


Iulink
URLhttps://www.inductiveuniversity.com/videos/tags-in-ignition/8.0
NameTags in Ignition






Tag Browser Tree

The Tag Browser is set up in an interactive tree structure with folders that can be expanded or collapsed to view more Tags. Click on the Expand   icon to expand any folder or the Collapse  icon to collapse the folder. In the example below, the pH Tag for Tower2 was expanded.


Tag Browser Toolbar

The Tag Browser toolbar has several options for working with Tags.

Add Tag

The Add  icon opens a context menu showing all the options to Browse Devices, add a Tag, Folder, UDT Instance or a UDT Definition. The new object is added under the Folder you selected, or as a sibling to the Tag you selected. This button is disabled if there is no selection. 

Browse Devices

With the Browse Devices, you can browse to find external PLC or OPC Tags. Click the Add  icon at the top of the Tag Browser to open the Browse Devices. You can then select Tags and move them to the Tag Browser to be used in the Ignition system. For complete information, see Creating Tags. 


Find/Replace

Clicking on the Search icon in the Tag Browser will open up the Designer's global Find/Replace screen. In the the example below, we searched for the Ramp9 Tag and limited the search to the default Tags.  Results are shown at the bottom of the screen. For additional information, see Find and Replace.



Refresh Providers

The Refresh Providers  icon refreshes all of the Providers in the Tag Browser. This is useful if you or others have modified Tags and do not see an update. In general, this button is not used very often.

Tag Provider Selector

The Tag Provider Selector is a dropdown menu with a list of available Tag Providers.  Use this selector to view the System Tags, Vision Client Tags, default Tags, or other Tag Providers you have in your project. 

On a new install of Ignition, a single "default" Tag Provider is created for you, but there are no Tags added to the "default" provider initially. You'll notice the "default" provider is in  bold.  The bold entry in the dropdown list is determined by the Default Provider for the project.  You can change the default provider in Project Properteries > Project > General > Tag Settings > Default Provider.  Save and restart the Designer, and the next time you open the Tag Provider in the dropdown of the Tag Browser, a different Default Provider will be displayed in bold. 

System, the Browsing Devices under the Add  icon is disabled.



More Options Menu

A More options  icon on the upper right of the Tag Browser, opens a dropdown menu of additional options.

Tag Groups

In the Tag Browser, the  Edit Tag Group opens the  Tag Group Editor window. Tag Groups dictate the rate of execution of Tags. This is where you set up your Tag Groups and scan rates. See Tag Groups for more information.

Import/Export

Ignition can export and import Tag configurations to and from the  JSON  ( JavaScript Object Notation ) file format. Use the  Import  icon or  Export   icon to import and export Tags in this Gateway. See Exporting and Importing Tags for more information.

Column Selector

The Tag Browser displays the Value and Data Type. The Value type is set by default.  To toggle any of the options, click on the  Column Selector  icon, then click the checkbox.
In the example below, the Tag values are shown next to the Tag names.




Right-Click Menu

Editing Tags is done mostly through the Tag Browser. The  Tag Browser allows you to right click on a Tag or folder to perform any of the following functions. Different objects will have different options available. The special Data Types folder is slightly different than a regular folder and will have even fewer options. 

  

Function

Description

Edit Tag

Disabled when a Folder is selected.

Opens the Tag Editor window so the Tag can be edited.

Edit (raw)

Disabled when a Folder is selected.

Opens a JSON editor, allowing you to view and edit the underlying JSON that makes up the Tag. 

RenameRenames the current selection.
DeleteDeletes the current selection.
CutCuts the current selection into the clipboard.
CopyCopies the current selection into the clipboard.

Copy JSON

Available for non-client tags only.

Copies the JSON for the selected Tags into the system clipboard. In addition, pasting the JSON into a different provider/designer will create or overwrite Tags.

Copy Tag PathCopies the currently selected Tag path into the clipboard.
PastePastes the content in the clipboard into the selected context.
New Tag

Disabled when a Tag is selected.

For Folders, this option opens a sub-menu to create a Tag or Tags.

FunctionDescription
New FolderCreates a new Tag folder.
Data Type Instance

Creates a new instance of an existing data type. The instance is linked to the parent type so when the parent changes, the instances are overwritten with the parent type changes.

Sub Menu - based on Data Types

New Standard Tag

Creates different types of Tags such as Derived, Expression, Memory, OPC, Query, and Reference Tags.

Sub Menu - Standard Tag Types


Multi-instance WizardCreates many instances of a UDT at the same time.

Export

Exports the selected Tags.
Import TagsImports Tags into the project.
EAMSends Tag to EAM Agents.
Restart TagAttempts to start / restart the selected Tag. If a folder is restarted, then all tags under the folder will restart.



Tag Traits

Certain settings or Tag configurations are visually represented next to the Tag in the Tag Browser.

 


The following icons enable you to note some important settings on the Tag at a glance. A description of the icons are listed below. 

IconSettingDescription

ScalingThe Scale Mode property under the Numeric Tag Properties section of the Tag Editor has been set to a value other than "Off." The value on the Tag will be scaled to some degree.

AlarmingAt least one alarm has been configured on this Tag.

Tag HistoryThis Tag has been configured to log data into the Tag Historian system.

Tag Event ScriptAt least one Tag Event Script has been enabled on this Tag.

LockShows the Tag has permissions enabled.

Image Added

InheritanceDenotes inheritance. Displays the Parent Type, name of the UDT and instance name (i.e., Parent Types: Motor UDT > Complex Motor).  Refer to UDT Inheritance Traits.

Image Added

OverrideDenotes that the property in the UDT instance overrides the parent property. Refer to Overriding Properties of the Parent UDT



Tag Editor

The Tag Editor is robust interface that contains all the properties that can be configured for Tags. In the Tag Editor, you set the Tag's name, value, numeric and meta data properties, security, alarming, history, and more. For information on all the settings in the Tag Editor, see Tag Properties.