Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


New_in
Version8.0.8



Ignition now supports Omron FINS devices. This driver does support both UDP and TCP transport protocols.

Connect Ignition to an Omron FINS Device via TCP

  1. Go to the Config section of the Gateway Webpage.
  2. Scroll down and select OPC UA > Device Connections.



  3. On the Devices page, click on Create new Device.
  4. Select Omron FINS/TCP, and click Next.
  5. Fill in the following fields:

    Name: FINS TCP
    Hostname: Enter the IP address, for example 74.125.224.72

    Leave the default values in the remaining fields.

  6. Click Create New Device.

The Devices page is displayed showing the FINS TCP device is successfully created and added to Ignition.


On_this_page




Connect Ignition to an Omron FINS Device via UDP

  1. Go to the Config section of the Gateway Webpage.
  2. Scroll down and select OPC UA  > Device Connections.
  3. On the Devices page, click on Create new Device.
  4. Select Omron FINS/UDP, and click Next.
  5. Fill in the following fields:

    Name: FINS UDP
    Bind Address: Enter the IP address of your Gateway, for example 74.125.225.10
    Remote Address: Enter the IP address of your Omron FINS device, for example 74.125.224.72

  6. Under FINS Settings set the following:

    FINS Source Node: The last octet of your IP address, for example 10 using the bind address above.
    FINS Destination Network: The address number of your FINS device typically configured in the routing table for your device. The valid range is 0-128.
    FINS Destination Node: The node number of your FINS device. This is typically the last octet of the IP address of the device, for example 72 in the example above.
    Fins Destination Unit: The unit number of your FINS device.

  7. Click Create New Device.

The Devices page is displayed showing the FINS UDP device is successfully created and added to Ignition.


Device Settings 


General


Name

Device name.

Description

Device description. 

Enabled

Default is set to true.


Connectivity



Hostname

The hostname or IP address of the device.

TCP Only

Port

The port your Omron device is listening on. The default is 9600.

TCP Only

Local Address

Address of network adapter to connect from.

TCP Only

Bind Address

The hostname or IP address of the Gateway.

UDP Only

Bind Port

The port you wish to create a UDP connection on for the Gateway. The default is 9600.

UDP Only

Remote Address

The hostname or IP address of the device.

UDP Only

Remote Port

The port your Omron device is listening on. The default is 9600.

UDP Only

Timeout

The request timeout, specified in milliseconds. The default is 2,000.

UDP & TCP


FINS Settings



FINS Source Network

The address number of the source network (the Ignition Gateway).

Valid value is an integer between 0 and 127. The default setting is 0.

FINS Source Node

The number of the source node (the Ignition Gateway), typically the last octet of the IP address.

Valid value in an integer between 0 and 254. The default setting is 0.

FINS Source Unit

The unit number of the source device (the Ignition Gateway).

Valid value is an integer between 0 and 255. The default setting is 0

FINS Destination Network

The address number of the destination network (the FINS device).

Valid value is an integer between 0 and 127. The default setting is 0.

FINS Destination Node

The number of the destination node (the FINS device), typically the last octet of the IP address and set via dials on the front of the device.

Valid value in an integer between 0 and 254. The default setting is 0.

Fins Destination Unit

The unit number of the destination device (the FINS device).

Valid value is an integer between 0 and 255. The default setting is 0


Request Optimization


Concurrent Requests

The number of requests that Ignition will try to send to the device at the same time. Increasing this number can sometimes help with your request throughput, however increasing this too much can overwhelm the device and hurt communications with the device.

Max Request Size

The maximum size of a request in bytes.

Max Gap Size

The maximum address “gap” to span when optimizing requests to contiguous address locations.

Write Priority Ratio

The number of write requests to execute for every read request, when an abundance of both are queued for execution.




New_in
Version8.0.11



Importing Addresses

As of version 8.0.11 a user interface was added to create import addresses. After import, you'll be able to browse the Tags in the Designer.

  1. Go to the Config section of the Gateway Webpage.
  2. Scroll down and select OPC UA  > Device Connections.
  3. On the Devices page, scroll to the OMRON FINS device. Click the More dropdown and choose addresses.

     

  4. On the next page, load the addresses from a CSV or TSV file. Click the Load Configuration button and choose a file.
  5. Click Load.



    You'll see the values load onto the screen.




  6. Click Save Configuration.  
  7. Once you save any changes made to the Tag mapping, you can view the Tags in the Designer OPC Browser.



Addressing

You also have the option to manually address tags via an Ignition OPC tag in the Ignition Designer.  See Ignition OPC UA Server Node Configuration for more information.

Data Areas

Area

Ignition Code

Omron Symbol Code

Native Size

CIO Area

CIO


Int16/UInt16

Work Area

WR or W

W

Int16/UInt16

Holding Bit Area

HR or H

H

Int16/UInt16

Auxiliary Bit Area

AR or A

A

Int16/UInt16

Timer Area

TIM or T

T

Int16/UInt16 or Bool

Counter Area

CNT or C

C

Int16/UInt16 or Bool

Index Register Area

IR

IR

Int32/UInt32

Data Register Area

DR

DR

Int16/UInt16

DM area

DM or D

D

Int16/UInt16

EM area

EM or Exx

E

Int16/UInt16


EM Area

Use EM for the current bank, or Exx for bank xx, where xx is 2 hex digits. Valid banks are E00 through E18 (25 total).

Data Types

BitBoolInt16
Int32Int64UInt16
UInt32FloatDouble
StringBCD16BCD32


Data Type Modifiers

ModifierOrder
@BEBig Endian Byte Order (default when not specified)
@LELittle Endian Byte Order
@HLHigh-Low Word Order
@LHLow-High Word Order (default when not specified)


Examples


Syntax Example

Note
 Items in curly brackets {} are optional.

Below is an example OPC Item path, representing how to manually specify an address in the device. 

Code Block
ns=1;s=[DeviceName]Area{<DataType>}Offset{.Bit}

When typing Addresses in using the Device's Address page on the gateway, the syntax looks like the following:

Code Block
Area{<DataType>}Offset{.Bit}


More Examples

Item Path
(OPC UA NodeId)
FINS Request
[myDevice]
CIO0
An Int16 at offset 0 in CIO area.
[myDevice]
CIO<Int32>1
An Int32 at offset 1 in CIO area.
[myDevice]
CIO<Int64>3.0
Bit 0 of an Int64 at offset 3 in CIO area.
[myDevice]
CIO<Int64@HL>3
An Int64 at offset 3 in CIO area in High-Low word order.
[myDevice]
TIM0
Present Value (16-bit) of Timer at offset 0.
[myDevice]
TIM<Bool>0
Completion Status (Bool) of Timer at offset 0.
[myDevice]
CNT0
Present Value (16-bit) of Counter at offset 0.
[myDevice]
CNT<Bool>0
Completion Status (Bool) of Counter at offset 0.
[myDevice]
DR0
An Int32 at offset 0 in DR area (32-bit by default).
[myDevice]
DR<Int64>0
An Int64 at offset in DR area.
[myDevice]
CIO<Int16[3]>0
An Int16 array of size 3 at offset 0 in CIO area.
[myDevice]
CIO<Int16[3]>0[1]
Element 1 of an Int16 array of size 3 at offset 0 in CIO area.
[myDevice]
CIO<String10>0
String of up to length 10 (string length in bytes) at offset 0 in CIO area.
[myDevice]
E001000
An Int16 from EM bank 0 at offset 1000.
[myDevice]
E00<Int16>1000
Also an Int16 from EM bank 0 at offset 1000, but with the an explicit DataType to make the address look less confusing.



Ignition OPC UA Server Node Configuration

You can also create OPC Nodes in Ignition’s OPC UA server manually via a CSV file on the Ignition Gateway itself with the following settings:

File Name: tags.csv
File Location: $ignitionHome/data/opcua/devices/$deviceName
File Format: Comma separated value file with the following columns:

  • Browse Path
  • Address
  • Description

Example File

Code Block
languagetext
Tag1,           CIO0, "First tag"
Foo/Tag2,       CIO1, "Second tag, in a folder"
Foo/Bar/Tag3,   CIO2, "In a couple of folders"

Use quotes on the description when it contains a comma (or whenever you like).

When adding or making changes to this file, a restart of the device is necessary for the changes to be picked up. This is done by editing the device and clicking Save.




Next_link