Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


What Is a Plugin?

Ignition Edge offers different plugins that each add unique functionality to the Edge Gateway. There are three plugins available: Panel, Enterprise, and MQTT. Each Edge installation must contain at least one plugin, but any combination of plugins can be used as well. Select the ones that you need and don't use the rest, just like the modules in a standard Ignition installation.

Panel

The Panel plugin is to provide a remote terminal for operators, usually to act as a backup in case there is a network failure. Panel provides up to two launchable clients for your Edge project, one local and one remote can be open at the same time. In addition, Panel provides alarm notification in a limited form. This means the Edge Gateway has only one email notification profile and no alarm pipelines. Ignition Edge Panel includes one week of data buffering for trending and local client fallback for mission-critical applications.


On_this_page




Configuring Alarm Notification

Because of this alarm limitation, when navigating to the Alarm Notification page in the Edge Gateway, you will be taken immediately to edit the Edge Notification Profile. In the settings, you can select an SMTP profile to use as well as a roster. Both your SMTP profiles and Rosters must be configured first, and the 'From' address of the notification email will be the email address that is used to log in to the SMTP server.

When a Tag goes into alarm, it will automatically go through this notification profile and be sent to all users in the selected roster. This alarm notification is one-way, meaning alarms can't be acknowledged from the notification email.

a_Edge - 2019-07-16_10-42-22.png


 Alarm Journal 

You can configure the settings for the Alarm Journal under the Alarming > Journal tab. The Edge alarm journal and audit log can sync under EAM.


New_in
Version8.0.7


Entries collected by the Alarm Journal and Audit Log on Edge gateways can now be forwarded to an Ignition gateway for long-term storage via EAM sync. Settings for this feature are available under the new Edge Sync Config page on Edge gateways. (Refer to the Data Sync settings under the Data Synchronization section).

a_Edge - 2019-07-16_10-59-52.png

Journal Properties

Main

EnabledBy default the journal profile is enabled.
Minimum PriorityOnly events equal to or greater than the specified priority will be stored. The default is Low. You can set the priority to be: Diagnostic, Low, Medium, High, and Critical.
Store Shelved EventsNot enabled by default. If enabled, events generated by "shelved" alarms will still be written to the journal system.

Stored Event Data

Alarm events consist of two main types of data: the primary information about the alarm, such as transition state, time, etc. , and the event data
The following settings specify what type of event data is stored:
Static ConfigBy default, it is not selected. If selected, will store the values of static alarmconfiguration. That is, the alarm properties that are not bound. These do not change during evaluation, only when a user modifies them in the Designer, and so they are not stored by default.
Dynamic ConfigIf selected, will store the values of dynamically bound alarm configuration properties. The value of these properties can change at any time, and the values at the time of the alarm are captured on the alarm event.
Static Associated DataIf selected, will store the values of non-bound associated data (properties created by the user) properties on alarm that do not change during execution.
Dynamic Associated DataIf selected, will store the values of dynamically bound associated data (properties created by the user) properties.

Data Filters


The following three properties interact via logical AND, meaning an alarm must meet the criteria for all three for it to be logged in the Journal. Thus, if you supply values for all three Data Filer properties, then an alarm must match the Filter by Alarm SourceFilter by Display Path, and Filter by Display Path or Source properties.

Example: if a Journal has values for all three properties, and an alarm only meets the requirements for Filter by Alarm Source and Filter by Display Path or Source, but not Filter by Display Path, then the alarm will not be logged to the Journal!

If you want to filter on both the Display Path and Source Path, you would want to use only one of the two following approaches:

  • Filter by Alarm Source and Filter by Display Path
  • Only use Filter by Display Path or Source

It is recommended to avoid using all three properties simultaneously on the same Journal.

Filter by Alarm SourceOnly events matching the source will be stored. Multiple sources to match can be comma separated. Leave blank to store events from all sources.
Filter by Display PathOnly events matching the display path will be stored. Multiple display paths to match can be comma separated. Leave blank to store events from all display paths.
Filter by Display Path or SourceOnly events matching the display path, if defined, will be stored. Multiple matches can be comma separated. If no display path is defined, only events matching the source will be stored. Leave blank to store all events.



Enterprise

The Enterprise plugin includes the Gateway Network, bringing in all of the remote distributed services that come with that. Other Ignition Gateways can use the distributed services to query Tag values, Tag history, and alarms from Edge Gateways with the Enterprise Plugin. However, Edge can only be the target of distributed services, meaning Ignition Gateways will have the ability to setup Remote History Provider connections to Edge, but Edge will not be able to setup a Remote History Provider connection to an Ignition Gateway.  The Enterprise plugin also allows you to setup the Edge Gateway as an EAM agent. This allows you to remotely monitor and manage Edge Gateways from a central Ignition Gateway.

Data Synchronization

The Enterprise plugin introduces Tag History Synchronization. Tag History Synchronization allows you to sync your history data from the Edge Gateway to a full Tag History Provider on an Ignition Gateway, allowing you to save past the one week data limit. The Edge Gateway will still only see the one week of data that it can hold internally, but it will allow you to store the data in a more permanent database that can be viewed from other Ignition systems. This is setup by navigating to the Tag History Sync page link at the bottom of the Edge Gateway Configure page.

Note
titleEnterprise Plugin

Edge Enterprise Plugin must be installed.


2019-12-13_10-50-41.png

2019-12-13_10-54-58.png

2019-12-13_11-38-50.png


Tag History Synchronization Properties

Here, you can setup the history sync to point to a Tag history provider in another Gateway that is connected through the Gateway Network.

Main

Settings


Remote Gateway NameThe gateway to target for remote synchronization.

Remote History Sync Enabled

Remote History Provider NameThe remote history provider to sync data to.
Remote History Sync EnabledWhether to send local tag history data to the remote system. The remote system must have the Tag Historian module installed, and allow remote storage. Default is false.
Max Batch SizeThe maximum number of data points that will be sent per batch to the remote gateway.
Sync FrequencyThe frequency with which data will be sent to the remote gateway. This setting will be used in conjunction with the sync schedule, if enabled.
Sync Frequency UnitsUnits are defined as milliseconds, seconds, minutes, hours, days, weeks, months, and years.
Enable ScheduleIf enabled, the data will only be synchronized during the times specified by the pattern provided.
Schedule PatternA comma separated list of time ranges that will determine when data will be sent over the network.

Remote Audit Settings

Remote Audit Profile NameThe remote audit profile to sync data to.
Remote Audit Sync EnabledWhether Remote Audit Sync is enabled. Default is false.
Sync FrequencyThe frequency with which data will be sent to the remote gateway. This setting will be used in conjunction with the sync schedule, if enabled.
Sync Frequency UnitsUnits are defined as milliseconds, seconds, minutes, hours, days, weeks, months, and years.
Enable Schedule

If enabled, the data will only be synchronized during the times specified by the pattern provided.

Schedule PatternA comma separated list of time ranges that will determine when data will be sent over the network.

Remote Alarm Journal Settings


Remote Alarm Journal NameThe remote alarm journal to sync data to.
Remote Journal Sync EnabledWhether Remote Alarm Journal settings are enabled. Default is false.
Sync FrequencyThe frequency with which data will be sent to the remote gateway. This setting will be used in conjunction with the sync schedule, if enabled.
Sync Frequency UnitsUnits are defined as milliseconds, seconds, minutes, hours, days, weeks, months, and years.
Enable ScheduleIf enabled, the data will only be synchronized during the times specified by the pattern provided.
Schedule PatternA comma separated list of time ranges that will determine when data will be sent over the network.


Tag History Sync is unique in that if the connection to the remote Ignition Gateway is severed, the Edge Gateway will use its week of storage as a Store and Forward buffer, allowing you to store up to a week of data before data is lost. Once the connection is restored, the Edge Gateway will send data over based on the max batch size and data frequency until all previous data is sent.



New_in
Version8.0.7


Sync Reset

Added a way to reset synchronization state for internal historian providers.
If you restored a gateway backup onto a system with existing locally "syncable" configuration files, then the backup may have IDs from a range beyond the local files. Use the Reset Sync actions to reset your local sync configuration.

To do a Sync Reset, go to Edge Gateways under Config > Enterprise Services > Sync Reset.

2019-12-13_12-38-18.png

2019-12-13_12-37-25.png



MQTT

The MQTT plugin allows this copy of Edge to push data directly into a Broker using the fast and lightweight MQTT data transfer protocol. In effect, this makes your computer (and whatever devices are attached to it) into a remote MQTT Publisher. If you are already rolling out new smart devices that connect to your Broker, this allows you to connect all of your legacy devices into the same system.

Installing the MQTT Plugin

  1. To install the Ignition Edge MQTT plugin, first download the MQTT Transmission Module from the Inductive Automation website. 
  2. Next go to the Config tab of your Edge Gateway. 
  3. On the Overview page, scroll down to the MQTT and click the Install+ button.

    2019-12-03_13-32-54.pngImage Modified

  4. Scroll down and click on Install or Upgrade a Module...

    2019-12-03_15-07-37.pngImage Modified

  5. Next click on Choose file.

    2019-12-03_15-16-03.pngImage Modified

  6. Navigate to the folder where you downloaded MQTT-Transmission-signed.modl.
  7. Click the Install button. 
  8. At the License agreement, click on I accept the terms in the License Agreement, then click the Accept License button.
  9. At the Trusted Certificates window, click I want to add this certificate to my trusted certificates and install the module. Then click the Add Certificate and Install Module button.

    2019-12-03_15-23-00.png

  10. You'll see a message indicating the module was successfully installed. And the Module will show up on the Module Configuration page in the Edge Gateway now. 

    2019-12-03_15-32-05.png

For more information, check out the documentation at the Cirrus Link website https://docs.chariot.io/display/CLD.
 



Next_link