User Manual

GETTING STARTED


MODULES AND PLATFORM


APPENDIX


TUTORIALS & HELPFUL TRICKS


STRATEGIC PARTNER LINKS

Sepasoft - MES Modules
Cirrus Link - MQTT Modules

RESOURCES

Inductive University
Ignition Demo Project
Knowledge Base Articles
Forum
IA Support
SDK Documentation
SDK Examples

ALL USER MANUAL VERSIONS

Ignition 8.1
Ignition 7.9
Ignition 7.8

Deprecated Pages

Employees

Sign In

Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
New_in
Version8.0.0


Scripting_function


Panel
titleDescription

Copies tags from one folder to another. Multiple tag and folder paths may be passed to a single call of this function. The new destination can be a separate tag provider.

Copying UDTs Across Tag Providers

When copying UDTs to a different provider, the destination provider must have a matching UDT definition. The function copies tags sequentially, so definitions can be placed earlier in the list, with instances following after:

Code Block
languagepy
# The '_types_' part of the path denotes the Data Types folder. You can retrieve the path to your UDT definition with right-click on 
# on the tag in the Tag Browser > Copy Tag Path.
udtDef = '[default]_types_/Motor'
udtInstances = '[default]UDT_Instances_Folder'


# When building the tag list, place the definitions in list before the instances
tags = [udtDef, udtInstances]

Tag Groups

Tag Groups will not be copied to the new provider, so the copied tags may not initially execute. This can be remedied by creating a matching Tag Group in the destination provider, either before or after the tags have been copied.

Remote Tag Providers

This function can move tags to or from a Remote Tag provider. In this case, the Tag Access Service Security settings on both providers must be set to ReadWriteEdit.

Panel
titleClient Permission Restrictions

Permission Type: Tag Editing

Client access to this scripting function is blocked to users that do not meet the role/zone requirements for the above permission type. This function is unaffected when run in the Gateway scope.

Panel
titleSyntax

 system.tag.copy(tags, destination, collisionPolicy)

  • Parameters

List tags - A List of Tag paths to move.

String destination - The destination to copy the Tags to. All specified tags will be copied to the same destination. The destination tag provider must be specified.

String collisionPolicy - [optional] The action to take when a tag or folder with the same path and name is encountered. Possible values include: "a" Abort and throw an exception, "o" Overwrite and replace existing Tag's configuration, "i" Ignore that item in the list. Defaults to OverwriteAbort.

  • Returns

List - A List of QualityCode objects, one for each tag in the list, that is representative of the result of the operation.

  • Scope

Gateway, Vision Client, Perspective Session

Panel
titleCode Examples
Code Block
languagepy
titleCode Snippet - Copy a Tag or Folder
# Define the tag/folder path(s).
tags = ['[default]Old_Tags/Subfolder' ]

# We'll move the tag/folder above to the new path
destination = '[default]New_Tags'

# If there is a collision with the destination, we'll abort the process.
policy = 'a'

# Copy the Tags
system.tag.copy(tags, destination, policy)
Panel
titleKeywords

system tag copy, tag.copy