User Manual

GETTING STARTED


MODULES AND PLATFORM


APPENDIX


TUTORIALS & HELPFUL TRICKS


STRATEGIC PARTNER LINKS

Sepasoft - MES Modules
Cirrus Link - MQTT Modules

RESOURCES

Inductive University
Ignition Demo Project
Knowledge Base Articles
Forum
IA Support
SDK Documentation
SDK Examples

ALL USER MANUAL VERSIONS

Ignition 8.1
Ignition 7.9
Ignition 7.8

Deprecated Pages

Employees

Sign In

Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.


The Direct Mode executes at a fixed rate which is defined by the slow polling rate setting. Every Tag that uses the Direct Tag Group will poll the PLC at the Rate setting at all times (24x7x365).

To Add a Direct Tag Group

  1. In the Tag Browser, click on the Timer  ()  icon to open the Tag Group Editor.

  2. On the bottom left side, click the green () icon to create a new Tag Group, and enter the values for the following properties:
    1. Name - enter a unique name for the Tag Group: Direct 5 Seconds
    2. Select the Mode: Direct
    3. Enter Rate: 5,000

  3. Click OK to save. 




  4. Now that you have your Tag Group created, let's add multiple Tags to the Tag Group. Go to your Tag Browser, find some Tags you want to add to the Tag Group. This example uses several Ramp Tags. Right click on the selected Tags, and click on Edit tag(s).



  5. This opens the Tag Editor window. It also shows you that you have multiple Tags selected. Select the Direct 5 Seconds Tag group from the dropdown, and click OK
    Image Removed
    Image Added

    That’s it! You created a new Direct 5 Second Tag Group and added your Tags. Just make sure you want to poll the 5 second values all the time (24/7) when you use the Direct 5 Seconds Tag Group.


On_this_page



Scroll html ignore


Iulink
URLhttps://www.inductiveuniversity.com/video/direct-scan-class?r=%2Fvideo%2Fsearch%2F%3Fq%3Ddirect%20scan%20class%26checked_videos%3D
NameDirect Scan Class

 


 

 

 

 

Direct Mode Properties

PropertyDescription
Common
NameUnique name of the Tag Group.
Mode

The Tag group executes at a fixed rate, defined by the Rate setting.

RateBase update rate, specified in milliseconds, at which Tags will be executed.
Note: If the rate is set to 0, the Tag group will not be executed.
OPC Settings
Data Mode

This mode dictates how OPC values are obtained. The default mode, Subscribed, is preferred because it is much more efficient than a read.

Subscribed
All OPC Tags in the Tag group will be subscribed according to the Tag group rate. Values will come in asynchronously as they change.

Polled
Tags will not be subscribed, but will instead be synchronously read each time the Tag group executes. This operation is less efficient, but allows more precise control over when values are obtained. This mode is particularly useful when collecting data over a slow or expensive connection for display. When combined with the one-shot execution mode above, and a static Tag tied to a momentary button, it's easy to create a manual refresh button on a screen that pulls data on-demand.

Read After Write

When enabled, a read request will be sent immediately after a write request. This means that the value on the Tag will be updated much quicker to reflect the latest written value.

Enabling this property is less efficient as a single write to a Tag becomes two separate requests. This is especially helpful with slower Tag groups as the Tags will show the latest value quicker than the normal execution would allow.

Optimistic Writes

If enabled, written values will be applied to the OPC Tag immediately. Normally, the system must receive confirmation that a write was successful from the device before the OPC Tag's value would change. This property changes the behavior by assuming the write went through unless the next read value or subscription update proves otherwise. Enabling this will make writes appear to execute much quicker.

Works in conjunction with the OPC Optimistic Write Timeout property below. If the OPC Tag does not receive confirmation that the new write was successful within the timeout, the Tag will fallback to the last known value. While in an ambiguous state, the Tag with have a quality of "Good (Provisional)".

This setting can be paired with the OPC Read After Write: the Tag will assume the newly written value, while an asynchronous read request is quickly sent out to confirm the write went through.

While the write is pending, values received from subscription activities will override the fallback value. Assuming an initial value of 0, if a write of 10 is applied to the OPC Tag, then the Tag will show a value of 10 until the system can confirm the new value. If a subscription update then returns a value of 5, the OPC Tag will fallback to 5.

Optimistic Write Timeout (MS)

The timeout period for Optimistic Writes. A value of 0 effectively disables the fallback functionality: the new value is maintained on the Tag until the next read or subscription activity.

History
Min Time Between SamplesMinimum time between samples (integer).
Min Time UnitsMinimum time in units is defined as: Milliseconds, Seconds, Minutes, Hours, Days, Weeks, Months, and Years.
Max Time Between SamplesMaximum time between samples (integer).
Max Time UnitsMaximum time in units is defined as: Milliseconds, Seconds, Minutes, Hours, Days, Weeks, Months, and Years.