Scripting_function



Panel
titleDescription

Edits an existing Tag in Ignition. This will not work on Client Tags, because there is a Client Provider for each project.

This can now be used to edit members of a nested UDT instance.


Panel
titleClient Permission Restrictions

Permission Type: Tag Editing

Client access to this scripting function is blocked to users that do not meet the role/zone requirements for the above permission type. This function is unaffected when ran from the Gateway scope.


Panel
titleSyntax

system.tag.editTag(tagPath, attributes, parameters, accessRights, overrides, alarmList, alarmConfig)

  • Parameters

String tagPath - The full path to the Tag you want to edit. For members of UDT instances, the tagPath will be the path to the UDT instance, with the overrides parameter listing out the member Tags to edit. Note: you can specify the Tag provider name in square brackets at the beginning of the parentPath string. Example: "[myTagProvider]MyTagsFolder". If the Tag provider name is left off then the project default provider will be used.

PyDictionary attributes - The Tag's configuration attributes.

PyDictionary parameters - The parameters for a UDT instance Tag.

String accessRights - The access rights for the Tags. Possible values are Read_Only, Read_Write, and Custom.

PyDictionary overrides - All of the overrides for a UDT instance Tag. The dictionary should be in the form of the names of member Tags as keys, with the values being a dictionary of properties/overrides ie. {'memberTagName':{dictionary of overrides}}.

String alarmList - List of legacy alarms for the Tag. The legacy alarm system was retired in 7.6.0. Newer systems should utilize the system.tag.editAlarmConfig function instead.

PyDictionary alarmConfig - The alarm configuration for the Tag. Note that this parameter cannot edit alarms on UDTs. Instead, the system.tag.editAlarmConfig function (which can also edit alarms on non-UDT Tags) should be used instead. See editAlarmConfig for details on how to use this parameter.

  • Returns

Nothing

  • Scope

All

Warning

If called in the Gateway scope, a Tag provider must be specified.

Associated attributes:



Panel
titleCode Examples


Code Block
languagepy
titleCode Snippet
# Example 1: Edit OPC Tag.

system.tag.editTag(tagPath="Tag1", 
attributes={"OPCServer":"Ignition OPC-UA Server", "OPCItemPath":"[MLX]N7:2"})


Code Block
languagepy
titleCode Snippet
# Example 2: Edit UDT instance parameters.
 
system.tag.editTag(tagPath="Tag5", parameters={"DeviceName":"CLX", "MotorNumber":2})


Code Block
languagepy
titleCode Snippet
# Example 3: Edit UDT instance called Tag8 and override certain properties of a member Tag called STATUS.
 
system.tag.editTag(tagPath="Tag8", overrides={"STATUS":{"ScanClass":"Default"}})


Code Block
languagepy
titleCode Snippet
# Example 4: Edit a nested UDT instance. Assuming the following:
# - A UDT instanced named 'ParentInstance' contains a nested UDT named 'ChildInstance'
# - ChildInstance contains a Tag (member) named 'ChildMember'

# The following script would override multiple properties on the ChildMember tag.
 
path = "ParentInstance/ChildInstance"
myOverrides = {"ChildMember":{"ScanClass":"Default", "Enabled":"false"}})

system.tag.editTag(tagPath=path, overrides=myOverride)


Code Block
languagepy
titleCode Snippet
# Example 5: Edit UDT instance called Tag8 and remove certain overrides from a member Tag called STATUS.
 
system.tag.editTag(tagPath="Tag8", parameters={"Param":"Something"}, 
overrides={"STATUS":{"ScanClass":None}})


Code Block
languagepy
titleCode Snippet
# Example 6: Enable history on a Tag, set the historical scanclass to "Default Historical", and set the History Provider to the "Data" provider.
 
system.tag.editTag(tagPath="Folder/Tag",attributes={"HistoryEnabled":True, "HistoricalScanclass":"Default Historical", "PrimaryHistoryProvider":"Data"})


Code Block
languagepy
# Example 7: Edit a Tag with an Alarm using the Legacy alarmList parameter.
alert = "myAlert;Medium_High;0.0;50.0;0;;;2.0;SEC$"
  
system.tag.editTag(tagPath = "Folder/Tag", alarmList = alert)