Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

 

 

With the Mobile module installed, you can launch your projects on any modern smartphone or tablet. This ability does not require any re-design of your projects – a mobile Client launches the same projects that the Vision Clients launch.

See the Mobile Module for more information.

 

To set the Mobile Module Settings

There is very little setup involved with the mobile module. Usually, with the exception of the the Server Address setting, you can keep all the the default settings.

  1. Go to the Configure section of the Gateway.
  2. Scroll down and go to Mobile > Settings page.

Here you will see all the settings and shown in the following table:

Settings

Java PathThis is the path to the Java executable on the Ignition Gateway server machine. The Java 7 JRE is required for the mobile module. A default value of “java” assumes that Java 7 is on the path and can be invoked merely with the “java” keyword.
Client MemoryThe amount of space allowed for each mobile client that is launched. Mobile clients are virtual clients that are launched on the server. All of the work is done on the server and transmitted to the mobile device so keep in mind that more mobile clients means more memory and CPU consumption on the server.
JVM OptionsCommand-line JVM options to use when launching mobile client VM's. Multiple options are separated with spaces. This option is made available mostly for troubleshooting by technical support staff, but if you are familiar with java and comfortable with command-line arguments then you can specify ones you may find useful here.
Environment VariablesHere you can specify any environment variables in the format of NAME=VALUE.
Idle VMs

The number of client VMs to startup and wait for incoming mobile connections. These will start when the gateway is started and sit idle until a mobile connection is made. This should be left at the default value of 0 unless it is taking a long time to launch a mobile client. It's important to note that the VMs that are sitting idle are not connected to a project so it will still take time to load the selected project.
Server AddressThis is the address to use when launching from the QR code on the launch page. This is a setting that often causes confusion. Initially this value is blank by default which results in the QR code pointing to the address of http://localhost:8088. Since Ignition is not running on your mobile device this address will not actually launch the mobile homepage. This should be set to the Ignition server address that can be reached by the mobile device.

Networking

Callback PortThe port that the VMs use to communicate to the Gateway on. By default this is set to 45900, but if this port is already in use then change this to an available port.
Callback InterfaceThe interface that mobile client VMs should use to communicate back to the Gateway on. By default this is localhost and makes use of the loopback adapter, however if this host doesn't have a loopback
adapter or if there are two network cards, set this to the IP address of the NIC that should be used for
local loopback.

 

Networking
Ajax
AJAX TimeoutThe max time, in milliseconds, that each request has to complete. The default is 10,000 (10sec).

Advanced Properties

 The Mobile Module also has an option to allow VNC connections. This allows certain thin clients that


do not support the Java Runtime Environment and also do not have an HTML 5 compatible browser to


launch Ignition clients. The settings listed under the advanced properties section all have to do with


configuring the VNC connection.

VNC Settings

Enable VNCAllows direct thin-client connection over VNC.
VNC PortThe port used for the VNC connection
Project NameThe Mobile Module only allows one of the projects on the Ignition gateway to be viewed through VNC

so you have to specify that project here. Unlike the normal mobile launch screen that allows you to

choose a project, the project that you specify in this setting will be automatically launched when you

connect via a VNC viewer application.
Project WidthThe width of the project when it's launched.
Project HeightThe height of the project when it is launched.






Next...