--- title: "system.tag.write" description: "Writes a value to a tag." --- # system.tag.write > Writes a value to a tag. :::note Deprecated This function was deprecated in 8.1.0. ::: This function is used in **Python Scripting**. ## Description Writes a value to a tag. Note that this function writes asynchronously. This means that the function does not wait for the write to occur before returning - the write occurs sometime later on a different thread. ## Client Permission Restrictions This scripting function has no [Client Permission](versioned_docs/version-8.1\ignition-modules\vision\vision-project-properties\vision-project-properties.md#vision-permissions-properties) restrictions. ## Syntax `system.tag.write(tagPath, value, suppressErrors)` - Parameters - String `tagPath` - The path of the tag to write to. - Object `value` - The value to write. - Boolean `suppressErrors` - A flag indicating whether or not to suppress errors. (optional, client-only). - Returns - int - 0 if the write failed immediately, 1 if it succeeded immediately, and 2 if it is pending. - Scope - All ## Code Examples ```python title="Example #1" # This code would go on a property change event for a numeric text field to calculate and write a value to a tag. if event.propertyName == intValue: calcValue = event.newValue * 2.5 system.tag.write("Tanks/tankHiSP",calcValue) ```