--- title: "system.alert.queryAlertStatus" description: "Queries the alerting system for the current status of all alerts." --- # system.alert.queryAlertStatus > Queries the alerting system for the current status of all alerts. ## Description Queries the alerting system for the current status of all alerts. By default, flatten mode is on, which means that you will get a single entry per alert path. If you turn flatten off, you'll get a row for each state of the alert. This can be important for alerts that have overlapping states. The results of this function are a dataset with the following columns: **System** - The system that issued the alert. **Display Path** - The custom display path (if any) for the alert. Will be the Path if no Display Path is configured. **State Name** - The state name for the alert. If flatten is true, this will be the highest severity active alert state. If no state is active, this will be the most recently cleared alert state. **Severity** - The severity, as a string. **Severity Code** - The severity as an integer. 0-4, low-high. **Active** - A boolean indicating whether this alert state is currently active. **Active Timestamp** - The time at which this alert went active. May be null. **Active Value** - The value that triggered this alert to go active. **Cleared** - A boolean indicating whether this alert is currently clear. **Cleared Timestamp** - The time at which this alert cleared. May be null. **Cleared Value** - The value that cleared the alert. **Acked** - A boolean indicating whether or not this alert has been acknowledged. **Ack Timestamp** - The time that the alert was acknowledged. May be null. **Ack user** - The user who acknowledged the alert. **Notes** - The notes field for the alert. **Flags** - A bitmask representing the current alert state. 0x01= Active, 0x02=Cleared, 0x04=Acknowledged. So if the alert is active and acknowledged, but not cleared, this will be 0x01 | 0x04 = 5 ## Syntax `system.alert.queryAlertStatus(system, path, stateName, minSeverity, maxSeverity, activeAndUnacked, activeAndAcked, clearAndUnacked, clearAndAcked, flatten, displayPath)` * Parameters * String `system` - Filter string to restrict results based on the alert system. * String `stateName` - Filter string to restrict results based on the alert state name. * Integer `minSeverity` - Minimum severity to return. Defaults to 0 (Low). * Integer `maxSeverity` - Maximum severity to return. Defaults to 4 (High). * Boolean `activeAndUnacked` - Whether or not to return alerts that are currently active and unacknowledged. Default is true. * Boolean `activeAndAcked` - Whether or not to return alerts that are currently active and have been acknowledged. Default is false. * Boolean `clearAndUnacked` - Whether or not to return alerts that are cleared and unacknowledged. Default is false. * Boolean `clearAndAcked` - Whether or not to return alerts that are cleared and have been acknowledged. Default is false. * Boolean `flatten` - If true, will flatten results so that there is only one entry per alert path, matching the highest active state. Default is true. * String `displayPath` - Filter string to restrict results based on the alert's display path. * Returns * Dataset - A dataset containing the alerts in the system that match the filters. * Scope * All ## Examples ```python title="Code Snippet" #This script will query the alert status for currently active alerts and push the results into a table. results = system.alert.queryAlertStatus(flatten=1,activeAndUnacked=1, activeAndAcked=1) event.source.parent.getComponent("Table").data=results ``` ```python title="Code Snippet" #This expression binding will return the count of currently active alerts with a severity of Medium or higher, checking once a second. runScript("system.alert.queryAlertStatus(activeAndAcked=1, minSeverity=2).rowCount",1000 ```