--- title: "Twilio SMS Notification" --- # Twilio SMS Notification > SMS notifications can be sent with the [Twilio Notification module](getting-started/modules-overview/additional-modules/twilio-alarm-notification.md). This does not require a cellular modem, but the Gateway must have Internet access and a Twilio account with SMS capabilities must be created (www.twilio.com). The Twilio account must then also be [defined in Ignition](../twilio-notification-profiles.md#define-a-twilio-account). :::caution This module requires the Alarm Notification module to be installed and enabled. If the Alarm Notification module is not installed or is disabled, this module will fault with a warning in the logs and display the state as "Faulted Missing Dependency" on the Platform > System > Modules page. ::: See the [system.twilio](../../../../../appendix/scripting-functions/system-twilio/system-twilio.md) section of the appendix for details on the scripting functions available for the Twilio SMS Notification Profile. ## Create a Twilio SMS Notification Profile 1. Go to the **Services** section of the Gateway Webpage. 2. Select **Alarming** > **Notification** from the menu on the left side. ![](2019-09-11_15-54-12.png) 3. Click on **Create Profile +**. 4. Select the **Twilio SMS Notification** profile type, and click **Next**. ![](2020-04-06_17-04-48.png) 5. Provide a name for the profile, and select a **Twilio Account** from the dropdown. 6. Set the other profile settings as desired. (See table below for a description of all settings.) 7. Click **Create Alarm Notification Profile**. Once your Notification profile is created, you can use it in an Alarm Pipeline. ### Twilio SMS Notification Profile Settings The following table describes the settings on the Alarm Notification Profiles page for a Twilio SMS Notification profile. #### General | Setting | Description | | ----------------------- | ----------------- | | Name | Name for this alarm notification profile. | | Description | Description of the profile.| | Enabled | Whether the profile is enabled or disabled. | #### Twilio | Setting | Description | | ----------------------- | ----------------- | | Twilio Account | Select a Twilio account from the dropdown list. | | Acknowledgement Allowed | Enables users to respond to notifications directly from the SMS message; also known as **Two-Way notification**. If enabled, the **Public Hostname** property in the Twilio Account must be configured. | #### Auditing | Setting | Description | | ----------------------- | ----------------- | | Auditing Profile | Select an audit profile from the dropdown list.|