--- title: "Scheduled Group" --- # Scheduled Group > You can log data to a database at specific times using the execution scheduling. You create the **Scheduled** group the same way as you create a basic **Historical** group. But instead of executing on a **Timer**, you select the **Schedule** radio button, and enter the times in the text box and the rate. The following table shows examples of how you can enter numbers in the text box: | Times | Rate | Result | |-------|------|--------| | 8, 11, 5pm | n/a | Group will execute 3 times at 8 in the morning, 11 in the morning, and finally at 5pm. | | 8 | n/a | Group will execute once at 8 in the morning. | | 8-10 | 1 hour | Group will execute at 8, 9, and 10 in the morning. | | 8-10, 17 | 1 hour | Group will execute at 8, 9, and 10 in the morning and once at 5pm. |