--- title: "Siemens" --- # Siemens > + **S7-300** > + **S7-400** > + **S7-1200** > + **S7-1500** ## Siemens Devices The Siemens drivers in Ignition support basic connections to S7 devices. Ignition connects to these PLCs via TCP/IP using the S7 protocol. Similar to Modbus and some Allen Bradley connections, the Siemens S7 devices do not support tag browsing. You can create S7 Tags manually in Ignition, or use Ignition's Tag import/export to create all of your Tags quickly in Excel or another spreadsheet program. Currently, Ignition has drivers for the following Siemens PLCs: ### Considerations for 1200 and 1500 Devices The following considerations and configurations changes must be made when using the S7-1200 and S7-1500 drivers. 1. Only global DBs can be accessed 1. The optimized block access must be turned off 1. The access level must be "full" and the "connection mechanism" must allow GET/PUT 1. Reads and Writes can not be used in TM/CT areas ## Connection to a Device 1. Go to the **Configure** section of the Gateway webpage. 1. Scroll down under **OPC-UA Server** and click **Devices**. 1. On the **Devices** page, find the blue arrow and click on **Create new Device**. 1. On the **Add Device Step 1: Choose Type** page, select the type of device. After making a selection, click **Next**. There are four types to choose from: + **Siemens S7-1500** - Which connects to Siemens S7-1500 PLCs over Ethernet. + **Siemens S7-1200** - Which connects to Siemens S7-1200 PLCs over Ethernet. + **Siemens S7-300** - Which connects to Siemens S7-300 PLCs over Ethernet. + **Siemens S7-400** - Which connects to Siemens S7-400 PLCs over Ethernet. 1. On the **New Device** page, leave all the default values and type in the following fields: + Name: **S7Device** + Hostname: type the **IP address** for the PLC 1. You can check the box for **Show advanced properties?** to see the additional settings, but you can keep all the defaults. 1. Click **Create New Device**. The Devices page is displayed showing the **Siemens** device is successfully created and added to Ignition. The **Status** will show as Disconnected and then Connected. Unlike other PLCs, but just like Modbus, Siemens devices do not support browsing, therefore you can not browse the tags by going to the **OPC Connections > Quick Client** in the **Configure** section of the Gateway. To see and browse the tags, you need to create the tags manually as described in the Addressing section. ## Configuring Siemens Addressing The S7 protocol does not support tag browsing. Therefore, you must configure all tags in the Designer. This can be done either manually, as needed, or by importing bulk using the Tags CSV import functionality. ### To manually specify each address 1. From the Designer, in the **Tag Browser**, right-click on **Tags** folder, and then go to **New Tag > OPC Tag**. 1. In the **Tag Editor** window, as an example, you can set the following values: + Name: **Tag** + Data Type: **Int4** + OPC Server: choose **Ignition OPC-UA Server** from the dropdown + OPC Item Path: `[S71200]IW0`, the `S71200` device name goes in the square brackets then you give the address to PLC which in this example is **IW0** (Word at Offset 0 in the Inputs area). The [Address Syntax](#address-syntax) section below, explains how your can construct these addresses. 1. Click **OK**. Now you can see the tag in the **Tag Browser**. ### Address Syntax You need a device name plus a tag address to create a tag. The device name is a known, but the tag address needs to be configured. Once you have both the device name and tag address you enter them in the in the **OPC Item Path** field of the **Tag Editor** window using the **[device_name]address** format, where **device_name** is the name of the device and **address** is the configured tag address which is described here. Tag addresses are made up of three different components: **Area**, **DataType**, and **Offset**. #### Areas |Area|Syntax| |:---|:---| |DataBlocks|DBn| |Inputs |I| |Outputs |Q| |Flags |M| |Timers|T| |Counters |C| #### Data Types |Data Type|Syntax|Signedness| |:---|:---|:---| |Bit|X|N/A| |Byte|B|Unsigned| |Char|C|Signed| |Word|W|Unsigned| |Int|I|Signed| |DWord|D|Unsigned| |DInt|DI|Signed| |Real|REAL|Signed| |String|STRING or STRING.LEN|N/A| #### Examples To form an address, you combine syntax for the desired Area and DataType with an Offset into that area. `Area + Data Type + Offset` |Address|Description| |:---|:---| |`IB0`|Byte at Offset 0 in the Inputs area| |`IW0`|Word at Offset 0 in the Inputs area| |`DB500,DI8`|DInt at Offset 8 in DataBlock 500| |`ISTRING24.50`|A String of length 50 starting at offset 24 in the Inputs area| |`IX20.3`|Bit 3 of the Byte at Offset 20 in the Inputs area| |`T0`|Timer at offset 0 (No DataType is specified for Timers)| |`C0`|Counter at offset 0 (No DataType is specified for Counters)| ### Offsets It is important to note that offsets are absolute. **IW0** and **IW1** share a byte. To get 2 consecutive, non-overlapping words you need to address **IW0** and **IW2**. ### Bits Bits are addressed by using the Bit DataType (X) and appending `.bit` to the end, where bit is in the range [0-7]. When addressing a Bit at a given offset, that offset is always treated as a Byte. ### Strings Strings are assumed to be in the S7 string format and have a max length of 210. ### Timers Timers are scaled up to a DWord and converted from S5 time format so they can represent the time in milliseconds without requiring any multipliers. When you write to a timer it is automatically converted from milliseconds into S5 time format for you. A DataType is not specified when accessing Timers. ### Counters Counters in the PLC are stored in BCD. The driver automatically converts to/from BCD for you and exposes any counter tags as UInt16 values. A DataType is not specified when accessing Counters. ## Device Settings ### General Settings |Setting|Description| |:---|:---| |Name|The name of the Device Connection| |Description|A description for the Device Connection. The description will appear on the Devices page on the Gateway.| |Enabled|Whether or not the connection is active. Disabling this setting terminates communication with the device.| ### Connectivity Settings |Setting|Description| |:---|:---| |Hostname|The hostname or IP address of the device.| |Timeout|The request timeout, specified in milliseconds. The default is 2,000.| ### Advanced Settings |Setting|Description| |:---|:---| |Port|The port to use when connecting to the device. The default is 102.| |PDU Size|Number of bytes to fit into PDU block of a single packet. Increasing this number can improve request throughput only if the processor supports a higher PDU Size. Varies from 240 and up to 960 depending on the device. The default is 240.| |Rack Number|The number of the rack that the device is positioned in. The default is 0.| |CPU Slot Number|The slot number assigned to the CPU. The default is 2.| |Reconnect After Consecutive Timeouts|After several consecutive timeouts, the Device Connection will attempt to reconnect to the Device. This setting determines how many consecutive timeouts must occur before reconnecting.|