This function is used in Python Scripting.

Description

Returns a sequence of all available schedule models, which can be used to return configuration information on the schedule, such as time for each day of the week.

Client Permission Restrictions

This scripting function has no Client Permission restrictions.

Syntax

system.user.getSchedules()

  • Parameters

Nothing

  • Returns

List - A list of schedules. Each schedule can be a BasicScheduleModel object, CompositeScheduleModel object, or another type registered by a module.

  • Scope

Gateway, Vision Client, Perspective Session

Code Examples
Code Snippet
# This example will print a list of all available ScheduleModels.
 
# This function handles recursive printing of the different schedule models. Modules can register more types than listed here.
def printScheduleInfo(aSchedule):
	if aSchedule.getType() == "basic schedule": 
		print "Basic schedule type: ",aSchedule.getName(), aSchedule.getDescription(), aSchedule.isAllDays(), aSchedule.getAllDayTime()
	elif aSchedule.getType() == "composite schedule":
		compositePieces = aSchedule.getModels()
		print "Composite schedule type:",aSchedule.getName(), aSchedule.getDescription(), " which is made up of..."
		for piece in compositePieces:
			printScheduleInfo(piece)
	else:
		print "Other schedule type: ", aSchedule.getName(), aSchedule.getDescription(), aSchedule.getType(), aSchedule.isObserveHolidays()


# The main function.
schedules = system.user.getSchedules()
for schedule in schedules:
	printScheduleInfo(schedule)
Keywords

system user getSchedules, user.getSchedules