This function is used in Python Scripting.

Description

Issues a freeze command on the given analog outputs at the given time for the specified duration.

Client Permission Restrictions

Permission Type: DNP3 Management

Client access to this scripting function is blocked to users that do not meet the role/zone requirements for the above permission type. This function is unaffected when run in the Gateway scope.

Syntax

system.dnp3.freezeAnalogsAtTime(deviceName, absoluteTime, intervalTime, indexes)

  • Parameters

String deviceName - The name of the DNP3 device driver.

Integer absoluteTime - The absolute time at which to freeze, in millis. 

Integer intervalTime - The interval at which to periodically freeze, in millis. 

List indexes - A list of specific indexes on which to issue the freeze command. An empty list will freeze all points. 

  • Returns

Nothing

  • Scope

Gateway, Vision Client, Perspective Session

Code Examples
# This example shows a request to freeze analog inputs at indexes 2 and 4,
#  5 minutes from the current time, with no interval.
from time import *
 
fiveMikes = (60 * 1000 * 5) + int(time() * 1000) #ms
system.dnp3.freezeAnalogsAtTime("Dnp3", fiveMikes, 0, [2, 4])
Keywords

system dnp3 freezeAnalogsAtTime, dnp3.freezeAnalogsAtTime