This function is used in Python Scripting.

Description

Cancels any number of alarm pipelines, specified by their event ids. Event ids can be obtains from the system.alarm.queryStatus function. Canceling a pipeline will not impact the alarm that triggered the pipeline. The alarm will still be active, but will drop out of alarm pipelines.

Client Permission Restrictions

Permission Type: Alarm Management

Client access to this scripting function is blocked to users that do not meet the role/zone requirements for the above permission type. This function is unaffected when run in the Gateway scope.

Syntax

system.alarm.cancel(alarmIds)

  • Parameters

List[String] alarmIds - List of alarm pipeline event ids (UUIDs) to cancel.

  • Returns

Nothing

  • Scope

Gateway, Vision Client, Perspective Session

Examples
Code Snippet - Cancelling an Alarm
# This example shows the basic syntax for cancelling an alarm.
 
system.alarm.cancel(['c27c06d8-698f-4814-af89-3c22944f58c5'])
Code Snippet - Cancelling All Currently Active Alarms
# To cancel all currently active alarms:
 
ids = []
results = system.alarm.queryStatus(state=["ActiveUnacked", "ActiveAcked"])
for result in results:
 id = result.getId()
 ids.append(str(id))
 
system.alarm.cancel(ids)