Skip to end of metadata
Go to start of metadata


Tag Quality

Ignition has Quality built into Tags automatically. Data Quality is the measure of the reliability of a particular Tag's data. If a Tag's quality is not Good, the value generally should not be trusted. In these cases an overlay will be shown on bound components. In addition, the Tag in the Tag Browser will also be decorated with a quality icon, signifying a non-good value. 

Tag Quality in the Designer

In the Tag Browser, find your Tag, expand it, and scroll down to the meta property called Quality. Here, you can check the quality of the Tag. This example shows a Good Quality Tag, meaning the Tag can be trusted.

 


One obvious indicator if the Tag is of bad quality is if there is a red error message next to the Tag in the Value column. Hover over the error message to see if there is any additional information about the error. You can also expand the Tag to see the quality issue. This example shows the Query Tag with with a Error Expression Evaluation which helps you resolve the issue promptly.  

 

On this page ...

IULocgo


Tag Quality and Overlays


Component Overlays

It is especially important in HMI screens to be able to gauge the health and accuracy of what is displayed at a glance. In a highly distributed system like Ignition, it is especially important as the client may be located at quite a distance (maybe across the world) from the physical process it is monitoring and controlling.

For these reasons, Perspective and Vision components display visual overlays for various reasons to indicate that the data they are displaying is not good, or pending a reply from the device. Each data binding that drives a component is evaluated for quality. If any of these qualities becomes poor, the Perspective or Vision component will show an overlay. The different overlays can mean different things, denoting their underlying cause. What they indicate is based on the Quality properties of Tags.  

Component overlays appear in the Designer workspace, Perspective Session, and Vision Client to let designers and operators know when there is a problem with one of the bindings on a component. What is cool about component overlays is that they not only tell you that there is a problem, but they also help diagnose the problem. Vision and Perspective overlay systems are similar, but each look a little bit different. 

The sections below describe in detail Perspective and Vision overlays. Each module has its own Tag Quality Code Reference Table displaying the error codes and what they mean.

Perspective Component Overlays

Perspective overlays give designers and operators a lot of information to help them diagnose and correct a problem. Component overlays look and behave slightly different in Designer Mode, Preview Mode, and in a Perspective Session. Each is described below.

IULocgo


Component Overlays

Component Overlays in Designer Mode

In the following example, you see the Cylindrical Tank and a LED Display component have overlays with a red border around them and an exclamation mark  icon. If you select the component, a red triangle will appear in upper right corner of the Property Editor giving the designer some information about the error. Hover over the red triangle to open the message box to identify the data quality error and cause . You'll also notice that the affected property (i.e., value) is highlighted in light red indicating this property is the one having a problem. If the error is binding related, click on the binding icon next to the property to open the Edit Binding window. 


Under the Binding Preview area, you can see there is a Configuration Error. If the problem is with a binding type, chances are you might be able to correct it here, or you may need to go directly to the Tag, or check other resources like a database, OPC server, etc.



Component Overlays in Preview Mode

Switch from the Designer mode to the Preview Mode. To put your active view in Preview Mode, press the Preview / Designer mode  icon in the top menubar. Components that have a problem will have a red overlay and exclamation mark around them. To see the error, click on the exclamation mark . This opens a message box that informs you that you have an error and identifies affected property. 


Component Overlays in a Perspective Session

Component overlays in a Perspective Session work the same way as they do in Preview Mode. The component with the problem will have a red overlay with an exclamation mark. Click on the exclamation mark to open the message box. It will identify the data quality error and affected property to help to identify the problem. To correct the problem, you'll have to go back to the Designer.


Quality Code Reference Table

There are four primary quality codes which quickly inform the user of the quality of the Tag: Good, Uncertain, Bad, and Error. 

Each quality code has a range of subcodes that provide more specific information about the value of the Tag. The following tables outline the primary data qualities. Quality codes are broken up into several ranges. Note that not every value within a range has a code: the space is there for future codes to be added. 

  • 0-225: Good quality. The value is generally considered reliable. 
  • 256 - 511 : Uncertain quality. Generally represents a value that was good, but the reliability is somewhat questionable. These are generally used when the system hasn't received a new value in a timely manner. 
  • 512 - 767: Bad quality. There's a problem with the value, but it's an "expected" or well recognized type of the problem is. For example, the trial expired or read access was explicitly denied. 
  • 768 - 1023: Error quality. There is a problem with the value, and the problem was completely unexpected. For example, a query on a query tag couldn't execute, but the Tag doesn't know why. More details on such errors are usually sent to a console somewhere, such as the Gateway's console. 
Good QualitySubcodesMeaning
Good_Unspecified0A generic "good" code. Generally used in conjunction with a matching good quality subcode, (1,2, or 192).
Good_Provisional1Good data that should not be considered valid over long periods of time. Provisional values will not cache.
Good_WritePending2Used when a write is in progress. Generally, values use this code until the system knows the write through successfully, which would then result in a 192 code.

Good

192

This data has met all criteria for being considered reliable.

Good_Overload202

This feature is new in Ignition version 8.1.2
Click here to check out the other new features

Represents good data that is being sampled slower than requested due to a resource limitation.


Uncertain Quality
Subcodes
256 - 261

Meaning
Uncertain256An unspecified degree of uncertainty exists in this value.
Uncertain_LastKnownValue257The current value is unavailable and represents the last known value.
Uncertain_InitialValue258Indicates that a subscription has been made and a good value should be arriving shortly.
Uncertain_DataSubNormal259Insufficient good-quality sources required for the derivation of this value.
Uncertain_EngineeringUnitsExceeded260Indicates that a value has gone beyond its configured engineering units.
Uncertain_IncompleteOperation261An async operation is currently pending and its result is unknown.

Bad Quality
Subcodes
512 - 767

Meaning
Bad512General quality for a bad quality.
Bad_Unauthorized513An unauthorized request was made for data that requires authorization.
Bad_AccessDenied514Data requested that requires credentials not held by the requesting user.
Bad_Disabled515Data source is currently not enabled.
Bad_Stale516Data is out-of-date based upon the requested refresh interval.
Bad_TrialExpired517The Trial Mode's timer expired.
Bad_LicenseExceeded518The license limit has been exceeded.
Bad_NotFound519Object requested was not found.
Bad_ReferenceNotFound520Derived or referenced value required an object which was not found.
Bad_AggregateNotFound521Requested aggregate was not found.
Bad_NotConnected522A connection required for this value is not currently connected.
Bad_GatewayCommOff523Connection to the Ignition Gateway is currently turned off.
Bad_OutofRange524This value exceeded its allowed range.
Bad_DatabaseNotConnected525database connection required for this value is not connected.
Bad_ReadOnly526The target is not writable / read only.
Bad_Failure527A "failure" code was received from the underlying system. Additional details may be in the diagnostic message. This generally does not indicate an exception, which would be handled by Error_Exception, but instead a simple failure from a system that can return success or failure.
Bad_Unsupported528The operation is not supported by the target.

Error Quality
Subcodes
768 - 1023

Meaning
Error768An unexpected error occurred while retrieving or calculating this value.
Error_Configuration769The source of this value is not configured correctly.
Error_ExpressionEval770The source expression was unable to be executed.
Error_TagExecution771The source Tag could not be executed.
Error_TypeConversion772The actual value was not able to be coerced into the configured data type for the source of this value.
Error_DatabaseQuery773database query required for this value caused an error upon execution.
Error_IO774An input/output error occurred while attempting to retrieve or calculate this value.
Error_TimeoutExpired775An async operation failed dure to a timeout.
Error_Exception776An exception was caught, and logged in the relevant system.
Error_InvalidPathSyntax777A path (i.e., Tag path, property path, etc.,) was not able to be parsed because the syntax is invalid.
Error_Formatting778Attempted formatting (i.e., numeric, date formatting) failed.
Error_ScriptEval779A script needed to create this value failed to execute.
Error_CycleDetected780Calculating the value involved an execution cycle.

Vision Component Overlay Chart

For legacy reasons, Vision has some quality codes that are different from the quality codes listed above. Specifically, Vision receives the codes above, but also performs some translations, mapping to the entries listed below.  E

QualityValueMeaning
OPC_Bad_Data0The data is not reliable, further data isn't available.
OPC_Config_Error4There is a problem with the OPC Server, or OPC Item Path on the Tag. 
OPC_Not_Connected8A connection required for this value is not currently connected.
OPC_Device_Failure12There was an issue with the device connection, making the value unreliable. 
OPC_Sensor_Failure16There has been a failure in the sensor from which the value is derived. 
OPC_Bad_Showing_Last20Received a bad quality from the OPC server. Also implies that the value represents the last known good quality value. 
OPC_Comm_Failure24Received a "communication failure" message from the OPC server. 
OPC_Out_Of_Service28The OPC server is reporting that the source of the data is not operational. 
OPC_Waiting32Waiting for the server to obtain values.
OPC_Uncertain64The server identifies the value as uncertain, but is unaware of the reason. 
OPC_Uncertain_Showing_Last68Whatever was updating this value has stopped doing so. The value represents the last known good value. 
OPC_Sensor_Bad80There has been a failure in the sensor from which the value is derived by the data source. 
OPC_Limit_Exceeded84The value is outside of the range of values defined for this parameter. 
OPC_Sub_Normal88The value is derived from multiple sources, and has less than the required number of Good sources. 
Good192The data has met all criteria for being considered reliable.
Unknown256The Tag has an unknown value, and a reason has not been provided. 
Config_Error300There is a problem with the Tag's configuration. The error log may provide more information as to the exact problem.
Comm_Error301There is a problem in communication somewhere between the Tag and its data source.
Expression_Eval_Error310The expression in the Tag generated an error during execution. The error log should provide more information on the error.
SQL_Query_Error311A database connection is required for this value, but there is an error with the SQL syntax driving the value. 
DB_Connection_Error312database connection is required for this value, and the connection is reporting some sort of error. 
Good (Provisional)320Temporary "Good" value. The value isn't cached because the underlying quality may differ than what appears on the Tag.
Tag_Exec_Error330There was an error when evaluating the Tag.
Type_Conversion_Error340The value of the Tag could not be converted to the requested data type. Check the assigned data type of the Tag.
Access_Denied403The Tag permission settings do not allow the current user to view the Tag.
Not_Found404The Tag, or a Tag referenced from inside of it, could not be found (incorrect reference path).
Disabled410The Tag's "enabled" property has been set to false.
Stale500The Tag has not been evaluated within the expected time frame. There is likely a deeper problem with the Tag provider.
Unknown600An unspecified degree of uncertainty exists in this value.
Write_Pending700Used when a write is in progress. Generally, values use this code until the system knows the write through successfully, which would then result in a 192 code.
Demo_Expired900The system driving the Tag is operating in demo mode and has timed out.
GW_Comm_Off901When viewing Tags in the Designer, the Tags will have this value if communication with the Gateway is turned off from the toolbar.


Vision Component Overlays

An overlay on a Vision component lets the operator know that they could be looking at a bad value for that Tag. When the overlay goes away and the values start coming in again, the operator knows that it's a valid Tag, and the values can be trusted.

Component Overlays in Designer Mode

In the following example, you see a red overlay with an icon in the top left corner of the selected LED Display component. The icon gives you a clue to the source of the problem. In this example, it is an SQL Database error.  In the Vision Property Editor, the Quality property is highlighted and you'll notice there is a "Error_DatabaseQuery" error message.

The overlays table in the next section show all the possible Vision overlays and what they mean. 


IULocgo


Tag and Component Overlays

Component Overlays in Preview Mode

Let's switch from the Designer mode to the Preview Mode. To put your active view in Preview Mode, press the Preview / Designer mode icon  in the top menubar. Components that have a problem will have a red overlay and an icon in the top left of the component overlay to indicate the problem. The overlay is identical to the overlay that is displayed in the Designer, but the component cannot be selected.    

Component Overlays in the Vision Client

Component overlays in a Vision Client work the same way as they do in Preview Mode of the Designer.  You have to look at the icon on the overlay to help you diagnose the problem. Go back to the Designer to correct the problem.

Vision Quality Code Reference Table

The following table outlines the primary data qualities. The most important is Good, and that has a value of 192. There are more values, but these represent the most common:

QualityValueMeaning
Type_Conversion_Error340

The value of the Tag could not be converted to the requested data type. Check the assigned data type of the Tag.

Tag_Exec_Error330There was an error when evaluating the Tag.
Stale500

The Tag has not been evaluated within the expected time frame. There is likely a deeper problem with the Tag provider.

OPC_Not_Connected8The OPC server driving the Tag is not currently connected OR a value has not yet been received by the Tag from the server.
OPC_Bad_Data0The data is not reliable, further data isn't available.
Not_Found404The Tag, or a Tag referenced from inside of it, could not be found (incorrect reference path).
GW_Comm_Off901When viewing Tags in the Designer, the Tags will have this value if communication with the Gateway is turned off from the toolbar.
Good (Provisional)320Temporary "Good" value. The value isn't cached because the underlying quality may differ than what appears on the Tag.
Good192The data has met all criteria for being considered reliable.
Expression_Eval_Error310

The expression in the Tag generated an error during execution. The error log should provide more information on the error.

Driver_Demo_Timeout900The system driving the Tag is operating in demo mode and has timed out.
Disabled410The Tag's "enabled" property has been set to false.
Config_Error300

There is a problem with the Tag's configuration. The error log may provide more information as to the exact problem.

Comm_Error301

There is a problem in communication somewhere between the Tag and its data source.

Access_Denied403The Tag permission settings do not allow the current user to view the Tag.


Tag Quality and Referenced Tags

When Tags reference other Tags, such as in expressions, they will often pass the worst sub-quality up as their own. For example, even though a particular Tag's expression executes without problem, if the expression references a Tag whose quality is "Bad", the expression Tag will also report "Bad."


Overlay Opt-Out

Choosing the Overlay Opt-Out option will ignore the quality of the chosen Tag, making it have no effect on the component's quality overlay. The Overlay Opt-Out option is located in the Tag bindings for both Perspective and Vision components. If this option is enabled, the operator will not see any overlays and will have no indication that the underlying Tag quality is something other than good.  A word of caution when you use the Opt-Out option because you always want to give the operator some indication that the values they are seeing on the screen can be trusted, and by opting out, you are removing that indicator for the operator. 





  • No labels