This function is used by Ignition's Expression language.

Description

This looks for lookupValue in the lookupColumn of dataset. If it finds a match, it will return the value from the resultColumn on the same row as the match. If no match is found, noMatchValue is returned. Note: The type of the value returned will always be coerced to be the same type as the noMatchValue.

Syntax

lookup(dataset, lookupValue, noMatchValue[, lookupColumn][, resultColumn])

  • Parameters

DataSet dataset - A dataset to search through.

object lookupValue - The value to look for.

object noMatchValue - The result value if no match.

object lookupColumn - Optional. The column to lookup. Can either be the column index or the name of the column. Defaults to 0.

object resultColumn - Optional. The column to pull the result value from. Can either be the column index or the name of the column. Defaults to 1.

  • Results

object - The value in the result column of the same row that the lookupValue was found, or the noMatchValue if a match was not found. The data type of this object will always be coerced to match the type of the noMatchValue parameter. 

Examples

The examples are based of a table that has the following data in it:

ProductPriceCategory
"Apples"1.99"Fruit"
"Carrots3.5"Vegetable"
"Walnuts"6.25"Nut"
Code Snippet
lookup({Root Container.Table.data}, "Carrots", -1.0) //returns 3.50
Code Snippet
lookup({Root Container.Table.data}, "Grapefruit", -1) //returns -1, the noMatchValue
Code Snippet
lookup({Root Container.Table.data}, "Walnuts", "Unknown", 0, "Category") //returns "Nut"
Code Snippet
lookup({Root Container.Table.data}, "Pecans", "Unknown", 0, 2) //returns "Unknown", the noMatchValue