Enum Reference

Almost every property in Ignition that is located in a dropdown list has an enumeration that starts at 0 and counts down the list. Below are the definitions of Tag property selections:

 Basic Tag fields

Tag Type

0OPC Tag
1

DB Tag - represents either a Memory, Expression, or Query tag.

Based on the value of the Expression Type 

2Client Tag
6Folder Tag
13Derived Tag

Datatype

String Value

Integer Value

Byte

Int1

0

Short

Int2

1

Integer

Int4

2

Long

Int8

3

Float

Float4

4

Double

Float8

5

Boolean

Boolean

6

String

String

7

DateTime

DateTime

8

Text

Text

10

Byte Array

Int1Array

17

Short Array

Int2Array

18

Integer Array

Int4Array

11

Long Array

Int8Array

12

Float Array

Float4Array

19

Double Array

Float8Array

13

Boolean Array

BooleanArray

14

String Array

StringArray

15

DateTime Array

DateTimeArray

16

Binary Data

ByteArray

20

Dataset

DataSet

9

Document

Document

29

Tag Group Modes

0Direct
1Driven
2Leased

Write Response

0Failure
1Success
2Pending

Quality

Data Quality

0Bad Data from OPC
4CONFIG_ERROR
8NOT_CONNECTED
12DEVICE_FAILURE
16SENSOR_FAILURE
20Bad, showing last value
24COMM_FAIL
28OUT_OF_SERVICE
32WAITING
64UNCERTAIN
68

UNCERTAIN showing last value

80SENSOR_BAD
84LIMIT_EXCEEDED
88SUB_NORMAL
28SERVER_DOWN
192Good Data
216Good, with local override
256OPC_UNKNOWN
300Config Error
301Comm Error
310Expr Eval Error
330Tag exec error (fsql)
340Type conversion error
403Access Denied
404Not Found
410Disabled
500Stale
600Unknown (loading)
700Write Pending

Expression Type

0None (Memory Tag)
1Expression
2Query


  `

  • No labels