Search

User Manual

Getting Started


Modules and Platform


Appendix


Tutorials & Helpful Tricks


Glossary


Strategic Partner Links

Sepasoft - MES Modules
Cirrus Link - MQTT Modules

Resources

Inductive University
Ignition Demo Project
Knowledge Base Articles
Forum
IA Support
SDK Documentation
SDK Examples

All Manual Versions

Ignition 8
Ignition 7.9
Ignition 7.8

Deprecated Pages

Skip to end of metadata
Go to start of metadata

There are 3 simulator drivers in Ignition, and all can be used to read and write tags without any network or PLC connection.

Generic Simulator

The generic simulator provides a variety of tags that offer different data types and value generation styles. For example, there are ramps, sine waves, and random values. Additionally, there is a set of static writable tags whose values will persist while the device is running.

There are no configurable settings for the generic simulator.

Simulator tags

Read OnlyStatic values that do not change for read only purpose.
Tag NameValue  
ReadOnlyBoolean1False  
ReadOnlyBoolean2True  
ReadOnlyShort11  
ReadOnlyShort22  
ReadOnlyInteger11  
ReadOnlyInteger22  
ReadOnlyInteger33  
ReadOnlyInteger44  
ReadOnlyInteger55  
ReadOnlyLong11  
ReadOnlyLong22  
ReadOnlyFloat11.1  
ReadOnlyFloat21.2  
ReadOnlyDouble11.1  
ReadOnlyDouble21.2  
ReadOnlyString1ABCDEFG"  
ReadOnlyString2"ZYXWVUT"  
WriteableStatic values that you can read/write to.
TagInitial Value  
WriteableBoolean1False  
WriteableBoolean2False  
WriteableShort10  
WriteableShort20  
WriteableInteger10  
WriteableInteger20  
WriteableLong10  
WriteableLong20  
WriteableFloat10  
WriteableFloat20  
WriteableDouble10  
WriteableDouble2 0  
WriteableString1'' (empty string)  
WriteableString2'' (empty string)  
RandomRandom values updating at some rate, they follow Java Random(rate) - rate is the seed.
Tag NameUpdate Rate  
RandomBoolean110 sec  
RandomBoolean210 sec  
RandomShort15 sec  
RandomShort25 sec  
RandomInteger11 sec  
RandomInteger21 sec  
RandomLong12 sec  
RandomLong22 sec  
RandomDouble110 sec  
RandomDouble210 sec  
SineDifferent sine waves with low, high, and period.
Tag NameLowHigh

Period (Time it takes to go from low to high then back to low)

Sine0-10010060 s
Sine1-101010 s
Sine205015 s
Sine3-406020 s
Sine4-10010040 s
Sine5 -10010060 s
Sine6-101010 s
Sine7.-203015 s
Sine8-406020 s
Sine9-8511540 s
RampRamp signals starting from some value going up to some value at the specified rate. When they reach their upper limit, they are reset to zero.
Tag NameLowHighPeriod (Time it takes to go from low to high)

Ramp0

0100075 s
Ramp1010010 s
Ramp2-2517515 s
Ramp31031020 s
Ramp4040040 s
Ramp5050060 s
Ramp6060012.5 s
Ramp7-569517.5 s
Ramp81081030 s
Ramp9-1089050 s
RealisticValues determined by adding a random number (between -10 and 10) to the current value.
Tag NameLowHighRate of Change
Realistic0-50505000 ms
Realistic1-5050500 ms
Realistic2-50501000 ms
Realistic3-50501500 ms
Realistic4-50502000 ms
Realistic5-50502500 ms
Realistic6-50503000 ms
Realistic7-50503500 ms
Realistic8-50504000 ms
Realistic9-50504500 ms

 

Allen Bradley SLC Simulator

The SLC simulator driver creates a simple device whose address structure mimics a basic SLC structure. There are currently no configurable parameters.

 

A simulator for use with the legacy IA Dairy Demo project. It has a ControlLogix like structure with Compressor, Tank, Motor tags and more.

  • No labels