In order to address individual bits in Ignition, you must create a separate OPC tag pointing directly to the specific bit in the PLC.
When the integer values that come from the OPC tags are a series of binary bits, it is then possible to address each bit. For example, an integer value can have a 16-bit binary representation as shown here:
| | |
---|
4096 | 0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0 | 212 = 4096 |
1025 | 1,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0 | 20 + 210 = 1025 |
Suppose a MicroLogix PLC is connected to a Gateway.
- From the Tag Editor window, create an OPC tag to have:
Data Type: Integer with a value of 1025
OPC Item Path: [MLX]B3:0
- Then create a new OPC tag with a Boolean value to the first bit of this tag as follows:
Data Type: Boolean with a value of 1 or True
OPC Item Path: [MLX]B3:0/0
(for Micrologic, you can specify the bit as: 0/0 or 0.0. That is, with a slash/ or a period.)
[MLX]B3:0/0
has a value of 1 or a Boolean value of True