Skip to end of metadata
Go to start of metadata
Description

Exports the contents of a dataset as a CSV file, prompting the user to save the file to disk.

Syntax

system.dataset.exportCSV(filename, showHeaders, dataset)

  • Parameters

String filename - A suggested filename to save as.

boolean showHeaders - If true (1), the CSV file will include a header row.

Dataset dataset - The dataset to export.

  • Returns

String - The path to the saved file, or None if the action was canceled by the user.

  • Scope

Client

Code Examples
Code Snippet
#This snippet would prompt the user to save the data currently displayed in a Table component to a CSV file, and would open the file (in an external program, presumably Excel) after a successful save.
 
table = event.source.parent.getComponent("Table")
filePath = system.dataset.exportCSV("data.csv", 1, table.data)
if filePath != None:
	system.net.openURL("file:///"+filePath.replace('\\','/'))
  • No labels

2 Comments

  1. Anonymous

    Is there a way to enter the File Path and bypass the user prompt?

    1. Yes, but to do that you would need to use the system.file.writeFile() function instead of exportCSV().